Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Only Molded Case Circuit Breakers (FA, KA, QB, LA, MA, NA Legacy Square DTM Circuit Breakers) Catalog 0601CT9101 R11/15 2015 Class 601 CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 100 Ampere Frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers © 1991–2015 Schneider Electric All Rights Reserved 2 11/2015
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers INTRODUCTION....................................................................................................................................5 Molded Case Circuit Breaker Types...................................................................................................6 Internal Operating Mechanisms..........................................................................................................
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers ACCESSORIES..................................................................................................................................116 Factory and Field Installation Types................................................................................................116 Shunt Trip........................................................................................................................................
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Introduction For PowerPactTM H-, J-, L-, M-, P- and R-Frame circuit breakers see class 611 and 612 catalogs on the Schneider Electric website, www.schneider-electric.com. This catalog introduces legacy thermal-magnetic circuit breakers, magnetic only circuit breakers, and molded case switches. Most of the legacy devices are obsolete but will be in service for many years.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Molded Case Circuit Breaker Types This catalog discusses the following types of molded case circuit breakers: — Thermal-magnetic, including current limiting circuit breakers — Magnetic only (Mag-GardTM) circuit breakers — Molded case switches • Thermal-Magnetic Molded Case Circuit Breakers Thermal-magnetic molded case circuit breakers are the most common overcurrent protection devices.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers • Magnetic Only Circuit Breakers Mag-Gard magnetic only circuit breakers comply with National Electrical Code (NEC) requirements for providing motor circuit protection when installed as part of a listed combination controller having motor overload protection.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Internal Operating Mechanisms The following mechanisms allow the circuit breaker to operate: — Thermal trip — Magnetic trip — Push-to-trip button — Shunt trip — Undervoltage trip Note: Shunt trip and undervoltage trip are described in the Accessories section.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers • Magnetic Trip The magnetic (instantaneous) trip element uses an electromagnetic assembly, in series with the load current, to trip the circuit breaker instantaneously (with no intentional delay) at or above a predetermined current value. During a short circuit of significant magnitude, the high level current passing through the conductor rapidly increases the magnetic field of the electromagnet which attracts the armature.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers International I/O (ON/OFF) markings appear on the face of each Schneider Electric molded case circuit breaker and molded case switch in addition to the standard ON/OFF markings to indicate handle position. When tripped, the handle assumes a center position. To reset the breaker, the handle is moved to the OFF position and then to the ON position.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers • Circuit Breaker Coordination To determine what level of coordination exists between molded case circuit breakers, a comparison of circuit breaker characteristic tripping curves is necessary. A coordination study is an organized effort to achieve optimum electrical distribution system protection by determining the appropriate frame sizes, ampere ratings, and settings of overcurrent protective devices.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Figure 6: Maximum Let-through I2t Energy Let-through I2t curves show the extent to which the current limiting circuit breaker limits energy let-through under short circuit conditions. The theoretical I2t let-through of symmetrical sinusoidal current can be calculated. At 100,000 A rms, this would be 83 x 106 A2 seconds for ½ cycle if NO CURRENT LIMITING DEVICE WERE IN THE CIRCUIT.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers • Tripping System Schneider Electric thermal-magnetic molded case circuit breakers have a permanent trip unit that contains a factory preset thermal trip element and a magnetic trip element in each pole. The thermal trip element is rms sensing. In circuit breakers with frame sizes greater than 100 A, the magnetic trip element is field adjustable. A single adjustment simultaneously adjusts the instantaneous trip point in each pole.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 3: Circuit Breaker Endurance Frame Size Amperes Full Load Operations No Load Operations 0–100 6,000 4,000 101–225 4,000 4,000 226–600 1,000 5,000 601–800 500 3,000 801–2500 500 2,000 2501–4000 400 1,100 — Calibration Retest Both the 200% and 135% thermal calibration tests are repeated.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers — Dielectric Withstand The circuit breaker is subjected to twice its rated voltage, but not less than 900 Vac. When the sample circuit breaker passes these tests, circuit breakers of the same construction can be marked or labeled with the higher current interrupting rating. • Switching Duty The switching duty (SWD) listing applies only to 15 A and 20 A circuit breakers rated at 277 Vac or less.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers A circuit breaker with a slash rating, such as 120/240 V or 480Y/277 V, shall be permitted to be applied in a solidly grounded circuit where the nominal voltage of any conductor to ground does not exceed the lower of the two values of the circuit breaker’s voltage rating and the nominal voltage between any two conductors does not exceed the higher value of the circuit breaker’s voltage rating.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 5: UL Listed Interrupting Ratings in kA (RMS Symmetrical Amperes) UL Listed Interrupting ratings (in kA) Ampacity Catalog Prefix Maximum Voltage 240 Vac 480 Vac 600 Vac 125 Vdc 250 Vdc 500 Vdc 600 Vac 25 18 14 10 10 — 480 Vac 25 18 — 10 10 — 240 Vac 10 — — 5 5 — 600 Vac 42 25 22 10 10 — Standard Interrupting 15–100 70–250 FA KA 125–600 LA 600 Vac 42 30 22 10 10 — 300–1000 MA 600 Vac
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers The ampere interrupting rating (AIR) of a circuit breaker is the highest current at rated voltage that the circuit breaker is intended to interrupt under standard test conditions. The interrupting rating is shown on the faceplate of the circuit breaker for each voltage level that the circuit breaker can use.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers The following procedure is used to determine the continuous current carrying capacity of a thermalmagnetic circuit breaker at ambient temperature other than 104 °F (40 °C) (see data bulletin Determining Current Carrying Capacity in Special Applications for more information): 1. Refer to the ambient rerating curves for the circuit breaker type. 2. Select the curve for the specific amperage rating of the circuit breaker involved.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers (Unless the circuit breaker is rated for operation at 100% of its rating). Therefore, the current carrying capacity of a 200 A kA circuit breaker operating under continuous load at 400 Hz would be 200 x 0.92 x 0.80 = 147 A. Figure 9: 400 Hz Thermal Rerating Multiplier At frequencies above 60 Hz, the interrupting capacity of thermal-magnetic circuit breakers is less than the 60 Hz interrupting capacity.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers UL Listed 500 Vdc Rated Circuit Breakers Schneider Electric has UL listed dc thermal-magnetic circuit breakers specifically designed for use on ungrounded dc systems having a maximum short circuit (loaded) voltage of 500 Vdc or a maximum floating (unloaded) voltage of 600 Vdc. This UL listed dc rating is available on FH. KH, LH, MH and PA molded case circuit breakers.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Catalog Numbers Square D brand circuit breakers by Schneider Electric are ordered by a catalog number that includes the breaker family, description, poles, voltage rating, amperage rating and suffix. The table below shows a typical catalog number broken down by components.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 8: Breakdown of Typical Catalog Number FA Circuit Breaker Family FY - 30 A Frame Note: FA - 100 A Frame “A” is replaced by letter “H” for High Interrupting KA - 250 A Frame “A” is replaced by letter “C” for Extra High Interrupting LA - 400 A Frame “A” is replaced by letter “I” for Current Limiting. (FA, KA.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 9: PowerPact Q-frame Catalog Numbering System 1 Number Segment Character Circuit Breaker Family Q Circuit Breaker Type (Interrupting Rating) Connection Type Poles 240 Volts Only Description B 10 kA D 25 kA G 65 kA J 100 kA A I-Line E Bolt-on I-Line F No lugs (Bus Connection) L Lugs on both ends M Lugs on ON (I) end only P Lugs on OFF (O) end only 2 Two-pole 3 Three-pole Q B L 3 2 250 4 2 L W 3
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers 100 Ampere Frame This section provides specific information on Schneider Electric 100 A frame thermal-magnetic molded case circuit breakers. For more information, see the “Introduction” in this catalog.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Selection Data Table 12: Ampere Rating 100 A Frame Unit Mount Circuit Breakers1 AC Magnetic Trip Settings Amperes One-pole Catalog No. Two-Pole Catalog No. Three-Pole Catalog No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 12: Ampere Rating 100 A Frame Unit Mount Circuit Breakers1 AC Magnetic Trip Settings Amperes One-pole Catalog No. Two-Pole Catalog No. Three-Pole Catalog No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 13: Ampere Rating 100 A Frame I-Line Circuit Breakers AC Magnetic Trip Settings Amperes One-pole1 Catalog No. Two-Pole 1 Catalog No. Three-Pole Catalog No. Standard Lug Kit Wire Range FA Standard Interrupting FY/ FA/FH One-pole 1-1/2 in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 13: Ampere Rating 100 A Frame I-Line Circuit Breakers (continued) AC Magnetic Trip Settings Amperes One-pole1 Catalog No. Two-Pole 1 Catalog No. Three-Pole Catalog No. Standard Lug Kit Wire Range FH High Interrupting FA/FH Three-pole FC Two- and Three-pole 4-1/2 in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Dimensions Figure 11: FAL, FHL, FCL 100 A Frame ( ( ( ) ( ( ) ) ( ( ( ( ) ( ( ( ( ) ( ) ( ) ) ( ) ) ) ) ( ) ( ( ) ) ( ) ( ) ( ) ) ( ) ( ) ) ( ) ( ) ( ) ( ) ( ) ) ( ) ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) FCL two-pole circuit breaker dimension is the same as a three-pole circuit breaker. ( ( ( ) ( ) ( ) ( ) ( ) ( ) ) ) Dimensions: in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Figure 12: FIL 100 A Frame ( ( ( ) ( ( ( ) ) ( ( ) ) ) ) ( ) ) ) ( ( ) ( ) ( ( ( ) ) ( ( ) ( ) ) ) ( ) ( ) ( ( ( ( ( ) ( ) ) ) ) ) ( ) ( ) Dimensions: © 1991–2015 Schneider Electric All Rights Reserved in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Tripping Curves FA/FH/FC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 650-1 CIRCUIT BREAKER INFORMATION MULTIPLES OF RATED CURRENT Circuit Breaker Prefix Maximum AC Voltage Number of Poles FA 240 1 1, 2, 3 FA 480 1 2, 2, 3 240 2, 3 480 2, 3 FC FC Continuous Ampere Rating 15–25 FA 600 2, 3 FA, FH 600 1 2, 2, 3 1 120 Vac maximum. 2 277 Vac maximum.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers FA/FH/FC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 650-2 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles FA 240 1 1, 2, 3 FA 480 1 2, 2, 3 240 2, 3 480 2, 3 FC FC 30 FA 600 2, 3 FH 600 1 2, 2, 3 1 120 Vac maximum. 2 277 Vac maximum.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers FA/FH/FC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 650-3 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Maximum AC Voltage Number of Poles FA 240 11, 2, 3 FA 480 12, 2, 3 FC 240 2, 3 480 2, 3 FC Continuous Ampere Rating 35–60 FA 600 2, 3 FH 600 12, 2, 3 1 120 Vac maximum. 2 277 Vac maximum.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers FA/FH/FC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 650-4 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Maximum AC Voltage Number of Poles FA 240 11, 2, 3 FA 480 12, 2, 3 FC 240 2, 3 FC Continuous Ampere Rating 60–80 480 2, 3 FA 600 2, 3 FH 600 12, 2, 3 1 120 Vac maximum. 2 277 Vac maximum.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers FA/FH/FC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 650-5 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Maximum AC Voltage Number of Poles FA 240 11, 2, 3 FA 480 12, 2, 3 FC 240 2, 3 480 2, 3 FC Continuous Ampere Rating 90 & 100 FA 600 2, 3 FH 600 12, 2, 3 1 120 Vac maximum. 2 277 Vac maximum.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 820-5 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles FI 20–30 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 820-6 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles FI 35–50 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 820-7 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage FI 60–100 600 Number of Pole 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT FY THERMAL-MAGNETIC MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 651-1 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles FY 15–25 277 1 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT FY THERMAL-MAGNETIC MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 651-2 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles FY 30 277 1 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Let-through Curves I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS FI 100 A Frame at 240, 480 and 600 Vac, 3Ø 20 A Curve No. 820-1 Peak Let-Through Current Ip and 820-2 Let-Through I2t development and UL test programs. MaximumH Peak Let-Through Current (Amperes) HBased on typical values obtained throughout the circuit breaker Curve No. 820-1 Available Short Circuit Current (RMS Symmetrical Amperes) development and UL test programs.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers I-LIMITER® CURRENT LIMITING CIRCUIT BREAKERS FI 100 A Frame at 240, 480 and 600 Vac, 3Ø 25–100 A Curve No. 820-3 Peak Let-Through Current Ip and 820-4 Let-Through I2t development and UL test programs. MaximumH Peak Let-Through Current (Amperes) HBased on typical values obtained throughout the circuit breaker Curve No. 820-3 Available Short Circuit Current (RMS Symmetrical Amperes) development and UL test programs.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers 225 / 250 Ampere Frame This section provides specific information on Schneider Electric 225 / 250 A frame thermal-magnetic molded case circuit breakers. For more information, see the “Introduction” in this catalog. Description Table 14: Description of 225 / 250 A Frame Circuit Breakers Circuit Breaker Description QB, QD, QG, QJ 100–225 A, 240 Vac, 50/60 Hz, two- and three-pole.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 16: 250 A Frame Interrupting Ratings Catalog Number Prefix Unit Mount UL Listed Interrupting Rating (kA) No. of Poles Cont. Ampere Rating AC Volts - RMS Symmetrical Amperes I-Line DC Volts Federal Specs. W-C-375B/GEN 120 120/ 240 240 480Y/ 277 480 600 125 250 500 IEC 60947-2 Icu/Ics (kA) AC Voltage 415/240 KAL KA 2, 3 70–250 42 42 42 25 25 22 10 10 — 19a, 20a 10/2.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 17: 250 A Frame Unit Mount Circuit Breakers (continued) Ampere Rating AC Magnetic Trip Settings Amperes 1 Two-Pole Catalog No. Three-Pole Catalog No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 18: 250 A Frame I-Line Circuit Breakers (continued) Ampere Rating AC Magnetic Trip Settings Amperes 1 Two-Pole 2 Catalog No. Three-Pole Catalog No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Dimensions Figure 13: KAL, KHL, KCL, KIL 250 A Frame ( ( ( ) ( ( ( ) ) ( ) ( ) ) ) ( ) ) ) ( ( ) ( ( ) ( ( ( ) ( ) ( ( ( ) ) ( ) ( ( ) ( ) ( ) ) ) ) ( ( ) ) ( ) ( ) ) ) Dimensions: in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Tripping Curves MULTIPLES OF RATED CURRENT KA/KH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 655-1 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles KA/KH 70–100 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT KA/KH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 655-2 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles KA/KH 110–150 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT KA/KH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 655-3 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles KA/KH 175–250 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT KC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 655-4 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix KC KC Continuous Ampere Rating 110–225 Maximum AC Voltage 240 480 Number of Poles 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT KC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 655-5 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix KC KC Continuous Ampere Rating 250 Maximum AC Voltage 240 480 Number of Poles 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers KH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 655-6 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Circuit Breaker Prefix Breaker Suffix KH 170C Continuous Ampere Rating Maximum AC Voltage Number of Poles 125 500 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 825-3 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles KI 110–225 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 825-4 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles KI 250 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers PowerPact Tripping Curves MULTIPLES OF RATED CURRENT POWERPACT Q-FRAME MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 734-4 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating QB, QD, QG, QJ QB, QD, QG QJ 70 Maximum AC Voltage Number of Poles 240 2 240 3 208Y/120 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers POWERPACT® Q-FRAME MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 734-5 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating QB, QD, QG, QJ QB, QD, QG QJ 80 Maximum AC Voltage Number of Poles 240 2 240 3 208Y/120 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers POWERPACT® Q-FRAME MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 734-6 CIRCUIT BREAKER INFORMATION MULTIPLES OF RATED CURRENT Circuit Breaker Prefix Continuous Ampere Rating QB, QD, QG, QJ QB, QD, QG QJ 90 Maximum AC Voltage Number of Poles 240 2 240 3 208Y/120 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers POWERPACT® Q-FRAME MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 734-7 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating QB, QD, QG, QJ QB, QD, QG QJ 100 Maximum AC Voltage Number of Poles 240 2 240 3 208Y/120 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers POWERPACT® Q-FRAME MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 734-8 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating QB, QD, QG, QJ QB, QD, QG QJ 110–150 Maximum AC Voltage Number of Poles 240 2 240 3 208Y/120 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers POWERPACT® Q-FRAME MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 734-9 CIRCUIT BREAKER INFORMATION MULTIPLES OF RATED CURRENT Circuit Breaker Prefix Continuous Ampere Rating QB, QD, QG, QJ QB, QD, QG QJ 175–225 Maximum AC Voltage Number of Poles 240 2 240 3 208Y/120 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers POWERPACT® Q-FRAME MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 734-10 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating QB, QD, QG, QJ QB, QD, QG QJ 250 Maximum AC Voltage Number of Poles 240 2 240 3 208Y/120 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Let-through Curves KI 250 A Frame at 240, 480 and 600 Vac, 3Ø 110–250 A Curve No. 825-1 Peak Let-Through Current Ip and 825-2 Let-Through I2t development and UL test programs. HBased on maximum values obtained throughout the circuit breaker MaximumH Peak Let-Through Current (Amperes) Curve No. 825-1 development and UL test programs.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS KI Series 2 250 A Frame at 240, 480 and 600 Vac, 3Ø 110–250 A Curve No. 825-5 Peak Let-Through Current Ip and 825-6 Let-Through I2t development and UL test programs. MaximumH Peak Let-Through Current (Amperes) HBased on maximum values obtained throughout the circuit breaker Curve No. 825-5 Available Short Circuit Current (RMS Symmetrical Amperes) development and UL test programs.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers 600 Ampere Frame This section provides specific information on Schneider Electric 600 A frame thermal-magnetic molded case circuit breakers. For more information, see the “Introduction” in this catalog.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 22: 600 A I-Line Mount Circuit Breakers Ampere Rating AC Magnetic Trip Settings Amperes 1 Two-Pole 2 Catalog No. Three-Pole Catalog No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Tripping Curves MULTIPLES OF RATED CURRENT LC THERMAL-MAGNETIC MOLDED CASE CIRCUIT BREAKERS SERIES 3 CHARACTERISTIC TRIP CURVE NO. 660-12 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles LC 450 240 600 2, 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT LC THERMAL-MAGNETIC MOLDED CASE CIRCUIT BREAKERS SERIES 3 CHARACTERISTIC TRIP CURVE NO. 660-13 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles LC 500 240 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT LC THERMAL-MAGNETIC MOLDED CASE CIRCUIT BREAKERS SERIES 3 CHARACTERISTIC TRIP CURVE NO. 660-14 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles LC 600 240 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS SERIES 3 CHARACTERISTIC TRIP CURVE NO. 830-19 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles LI 300 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS SERIES 3 CHARACTERISTIC TRIP CURVE NO. 830-20 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles LI 350 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS SERIES 3 CHARACTERISTIC TRIP CURVE NO. 830-21 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles LI 400 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS SERIES 3 CHARACTERISTIC TRIP CURVE NO. 830-22 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles LI 450 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS SERIES 3 CHARACTERISTIC TRIP CURVE NO. 830-23 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles LI 500 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS SERIES 3 CHARACTERISTIC TRIP CURVE NO. 830-24 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles LI 600 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Let-through Curves I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS LI Series 2, 3 and LXI Series 2B, 3B 400 A Frame at 240, 480 and 600 Vac, 3Ø 300–400 A LXI Series 2B, 3B 250 A Frame at 240, 480, and 600 Vac, 3Ø 100–250 A Curve No. 830-15 Let-Through I2t and 830-16 Peak Let-Through Current Ip development and UL test programs.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers I-LIMITER CURRENT LIMITING CIRCUIT BREAKERS LI Series 2, 3 and LXI Series 2B, 3B 600 A Frame at 240, 480 and 600 Vac, 3Ø 450–600 A Curve No. 830-17 Let-Through I2t and 830-18 Peak Let-Through Current Ip development and UL test programs. TypicalH Let-Through I2t (Amperes2 Seconds x 106) HBased on typical values obtained throughout the circuit breaker Curve No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers 800 / 1000 Ampere Frame This section provides specific information on Schneider Electric 800 / 1000 A frame thermal-magnetic molded case circuit breakers. For more information, see the Introduction in this catalog.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 25: 800 A I-Line Circuit Breakers (continued) Ampere Rating AC Magnetic Trip Settings Amperes 1 Two-Pole 2 Catalog No. Three-Pole Catalog No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Dimensions Figure 15: ( ( MAL, MHL 800 / 1000 A Frame ( ) ( ) ( ) ( ) ) ) ( ) ( ) ( ( ) ( ) ( ) ( ( ) ( ) ( ) ( ) ) ) ( ) Dimensions: ( ) © 1991–2015 Schneider Electric All Rights Reserved in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Tripping Curves MULTIPLES OF RATED CURRENT MA/MH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 665-1 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles MA/MH 125–450 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT MA/MH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 665-2 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles MA/MH 500–600 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT MA/MH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 665-3 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles MA/MH 700–1000 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT MH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 665-4 CIRCUIT BREAKER INFORMATION Circuit Circuit Breaker Prefix Breaker Suffix MH 31DC Continuous Ampere Rating Maximum DC Voltage Number of Poles 450 500 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT MH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 665-5 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Circuit Breaker Suffix Continuous Ampere Rating Maximum DC Voltage Number of Poles MH 32DC 33DC 500 600 500 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 665-6 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Circuit Breaker Prefix Breaker Suffix MH 35DC 36DC 39DC 40DC Continuous Ampere Rating Maximum DC Voltage Number of Poles 700 800 900 1000 500 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT MA/MH FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 665-7 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles MA/MH 1200 600 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT MH THERMAL-MAGNETIC MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 665-8 CIRCUIT BREAKER INFORMATION Circuit Circuit Breaker Prefix Breaker Suffix MH 40DC Continuous Ampere Rating Maximum DC Voltage Number of Poles 1200 500 3 This curve is to be used for application and coordination purposes only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers 1200 Ampere Frame This section provides specific information on Schneider Electric 1200 A frame thermal-magnetic molded case circuit breakers. For more information, see the “Introduction” in this catalog.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Selection Data Table 29: 1200 A Unit Mount Circuit Breakers Ampere Rating AC Magnetic Trip Settings Amperes Two-Pole Catalog No. Three-Pole Catalog No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Dimensions Figure 16: NAL, NCL 1200 A Frame ( ) ( ( ) ) ( ) ( ( ) ( ) ( ) ( ) ) ( ( ( ( ( ) ) ( ) ( ) ) ( ( ) ) ) ( ) ( ( ) ) ( ( ) ) ) ( ) ( ) Dimensions: in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Tripping Curves MULTIPLES OF RATED CURRENT NA FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 670-6 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles NA, NC 600 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT NA FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 670-7 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles NA, NC 700 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT NA FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 670-8 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles NA, NC 900 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers NA FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 670-9 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles NA, NC 800 & 1000 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT NA FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 670-10 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles NA, NC 1200 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers 2000 / 2500 Ampere Frame This section provides specific information on Schneider Electric 2000 / 2500 A frame thermal-magnetic molded case circuit breakers. For more information, see the “Introduction” in this catalog.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 33: Ampere Rating 2000 A Unit Mount Circuit Breakers (continued) AC Magnetic Trip Settings Amperes 1 Low High Two-Pole, 600 Vac Three-Pole, 600 Vac Frame Only Rating Columns Two Per Kit Frame Only Rating Columns Three Per Kit Catalog No. Kit Catalog No. Catalog No. Kit Catalog No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Dimensions Figure 18: PAF, PHF 2000 A Frame ( ( ( ) ) ) ( ( ) ) ( ( ( ( ) ( ) ) ) ( ) ( ) ( ( ) ( ) ) ) ( ( ) ( ( ) ( ) ) ( ) ( ) ( ) ( ) ( ) ( ) ) ( ) Dimensions: in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Figure 19: Circuit Breaker with Terminal Pads—PALTB for PAF, PHF A Frame ( ) ( ) Do not run cables in shaded areas ( ( ) ( ) ( ( ( ) ( ) ) ) ( ( ( ) ) ( ) ( ) ( ) ( © 1991–2015 Schneider Electric All Rights Reserved ( ) ) ( ) ( A - Push-to-Trip Button B - Mounting Plane C - Rear Support D - Front Support ) ) ( ( ) ) ( ( ) ) ( ) ) Dimensions: in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Figure 20: PCF 2000 A Frame ( ( ) ( ) ( ) ) ( ) ( ) ( ) ( ( ) ) ( ( ) ) Push-to-Trip ( ( ( ) ( ( ( ) ( ) ( ) ) ( ) ) ) ( ( ) ) ( ) ( ) ( ) Dimensions: ( ) ( in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Tripping Curves MULTIPLES OF RATED CURRENT PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 675-1 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PA, PH 600 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 675-2 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PA, PH 700 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 675-3 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PA, PH 800 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 675-4 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PA, PH 1000 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 675-5 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PA, PH 1200 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 675-6 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PA, PH 1400 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 675-7 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PA, PH 1600 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers MULTIPLES OF RATED CURRENT PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 675-8 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PA, PH 1800 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 675-9 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PA, PH 2000 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 676-01 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PC 1600 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 676-02 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PC 1800 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 676-03 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PC 2000 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers PA\PH\PC FAMILY MOLDED CASE CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 676-04 MULTIPLES OF RATED CURRENT CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles PC 2500 600 2, 3 This curve is to be used for application and coordination purposes only. The EZ-AMP overlay feature at the bottom of the page should be used during coordination studies.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Accessories This section describes the UL listed accessories available for Schneider Electric thermal-magnetic molded case circuit breakers, Mag-Gard magnetic only instantaneous trip circuit breakers and molded case switches. These accessories increase application versatility and meet the demands of modern electrical distribution systems.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers The table below shows suffix numbers for the following combinations of factory installed accessories for the FA, FH, FC, FI, KA, KH, KC, and KI thermal-magnetic circuit breakers, magnetic only circuit breakers and molded case switches. Additional combinations are available; please contact the Schneider Electric Customer Care Center at: 1-888-778-2733.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Suffixes for Factory Installed Accessories1 (continued) Table 36: Shunt Trip Device Suffix 24 Vdc Shunt Trip 48 Vdc 24 Vac 120/240 Vac 277/480 Vac Undervoltage Trip Undervoltage Trip 24 Vdc 120 Vac 48 Vdc 240 Vac Auxiliary Switches 1A-1B 2A-2B 1352 X 1354 X2 Not Compatible With: 3A-3B 1364 1218 1 The FA one-pole Circuit Breaker is not included in this table. 2 Circuit breaker has 2 sets of 2A2B auxiliary contacts.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers • Field Installable Accessories Field installable accessories can be installed, interchanged or replaced in the field without affecting the circuit breaker’s UL listing or interrupting ratings. Field installable accessories cannot be used in a mounting location or a pole that has a factory installed only accessory. Field installable electrical accessories and circuit breakers are shipped separately.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Figure 21: Ground Fault and Shunt Trip Wiring Diagram Shunt Trip Wiring Diagram Color Code Black Leads Table 39: Shunt Trip Electrical Specifications1 Voltage Rating AC DC 1 Ground Fault Shunt Trip Wiring Diagram Color Code Orange Maximum Current in Milliamps (RMS) Coil Burden Max. VA Minimum Recommended Supply Transformer (VA) 24 850 (3650) 20.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Undervoltage Trip The undervoltage trip accessory reduces the possibility of damage to the electrical equipment when a reduction or loss of system voltage occurs.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Undervoltage Trip Time-delay Unit The undervoltage trip time-delay unit, when connected in series with a 120 Vac undervoltage trip, introduces an adjustable time delay of 0.1 to 0.6 seconds in the release of the undervoltage trip coil. This prevents momentary voltage fluctuations from releasing the undervoltage trip coil and nuisance tripping the circuit breaker.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Auxiliary Switch The auxiliary switch accessory monitors the circuit breaker’s contact status and provides a remote signal indicating whether the contact is open or closed. When the circuit breaker is in the OFF or tripped state, the auxiliary switch’s A contact is open and the B contact is closed. When the circuit breaker is ON, the B contact is open and the A contact is closed.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Alarm Switch The alarm switch accessory monitors the circuit breaker’s trip status and is used to provide a remote warning signal indicating the circuit breaker has tripped. This signal can be used in conjunction with a horn, pilot light or some other indicator. The contact on the standard alarm switch is open when the circuit breaker is in the OFF or ON position and is closed when the circuit breaker is in the tripped position.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Micrologic Ground Fault Module The Micrologic Ground Fault Module (GFM) is a UL listed self-powered ground fault sensing device that signals a circuit breaker ground fault shunt trip. It is available for use with unit mount or I-Line construction circuit breakers.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Standard features include: — All GFMs supplied for I-line mounting, are easily converted to unit mount by removing the I-line brackets. — Molded case circuit breakers using the GFM require a ground fault shunt trip (add suffix G to the circuit breaker catalog number when ordering). — All GFMs must be used with a three-pole circuit breaker. — Up to 200,000 A short circuit withstand rating at 600 Vac.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Figure 22: Ground Fault Module Dimensions ( ) ( ( ) ( ) ) ( ( ( ( ( ) ( ( ( ( ( ) ) ( ) ) ( ) ) ( ) ( ) ( ( ) ( ) ( ) ) ) ( ( ) ) ( ( ) ) ( ) ) ( ) ( ( ) ) ( ) ) ) ( ) ( ) ( ) ) ( ) ( ) ( ) ( ) ( ) Dimensions: in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers • Top Mount Electrical Operators (MO2) Top mount electrical operators are field installable on KA, KH, KC, KL, Q4, LA, LH, MA, MH, PA, PH and PC families of circuit breakers. They are intended for use on indoor, NEMA Type 1 applications. The top mount electrical operator requires a single pole, double throw switch and the proper control voltage.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Figure 23: Electrical Operator Side Mount Dimensions and Wiring Diagram Electrical Operator Wiring Diagram FA/KA Mounting Diagram Circuit Breaker with Electrical Operator LA/MA Mounting Diagram Table 49: Electrical Operator Electrical Operator Mounting Dimensions, Inches (mm) A in. B mm in. C mm in. D mm in. E mm in. F mm in. G mm in. H mm in. mm FAMO1 0.40 10.16 10.20 259.08 10.69 269.24 0.40 10.16 7.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Figure 24: Top Mount Electrical Operator Dimensions and Wiring Diagrams ( ( ( ( ) ) ) ( ) ( ( ( ) ( ( ( ( ( ) ( ( ) ( ( ( ) ) ( ) ) ) ) Mounting Dimensions for Electrical Operator ( ) ( ( ) ) Mounting Dimensions for Electrical Operator ( ) ) ) ) ( ) ) ) ( ) ) ( ( ) ( ) ( ( ) ( ) ) ( ) ) Mounting Dimensions for Electrical Operator Mounted on KAL, KHL, FIL, or KIL Circuit Breaker or
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Figure 25: PAMO2 Electrical Operator Suggested Wiring Diagrams Control Voltage: Switches shown in the suggested wiring diagrams can be, • • • 7.00 (178) 7.60 (193) Momentary contact, Solid state contacts Continuous contracts. 10.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Circuit Breaker Handle Accessories Several handle accessories are available to lock the circuit breaker. See table below to select the desired accessories. Table 50: Circuit Breaker Handle Accessories—Selection Data Accessories Padlock Attachment Handle Padlock Attachment Handle Extension Handle Extension & Padlock Attachment Handle Tie California Title 24 Combination Handle Tie & Lock-off Locks Circuit Breaker Circuit Breaker No.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Walking Beam Mechanical Interlock The walking beam mechanical interlock is used with two circuit breakers to maintain essential loads during power outages. It is UL listed for FA, KA, LA and MA circuit breakers, 15 A through 1000 A. Manual and automatic transfer schemes use these interlocked circuit breakers.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers • Dimensions The dimensions shown below are for two unit-mounted circuit breakers that are installed on the appropriate mounting pan include the walking beam assembly. The dimensions also show the electrically operated version. Requires two circuit breakers with WB suffix, one walking beam assembly and one mounting pan. Table 53: Electrical Operator Mounting Dimensions Dimensions Circuit Breaker A B C D E F G H in. mm in.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Operating Mechanisms • Door Mounted Type L door mounted, variable depth operating mechanisms are kits featuring heavy duty, all metal construction with trip indication. All of the operating mechanisms can be padlocked in the OFF position when the enclosure door is open. The kits include handle assemblies, padlocks, door drilling template and shafts.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers UL Listed Terminations Schneider Electric supplies all thermal-magnetic molded case circuit breakers, Mag-Gard instantaneous trip circuit breakers and molded case switches (1200 A frame and smaller) with mechanical-type aluminum alloy lugs suitable for use with either aluminum or copper wire. I-line circuit breakers are supplied with mechanical-type lugs on the OFF end.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers AL50FA AL100FA AL800MA Table 56: 1 AL800MA7 AL400LA AL400L7 AL1000MA AL1200NE6 Mechanical Lug Kit Wire Ranges and Torques—Selection Data1 No. of Lugs Per Kit Circuit Breaker AL50FA 3 AL100FA4 Lug Kit AL250KA Number of Wires Per Lug and Wire Ranges Lug Mounting Screw Torque Wire Binding Screw Torque No. Wires Domestic Metric lb-in. N•m Wire FA, FH, FI 1 #14–#4 Cu or #12–#4 Al 2.5–25 mm2 4–25 mm2 40 4.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers VC250KA3 Table 57: Lug Kit VC400LA3 Versatile Compression Lug Kit Wire Ranges and Mounting Screw Torques—Selection Data No. of Lugs Circuit Breaker Per Kit Versatile System Wire Ranges 1 Lug Mounting Screw Torque Versa-Crimp Tool Type Mounting Hole Dia. Domestic Metric lb-in. N•m in. mm VC100FA 1 FA, FH, FC, FI #8–1/0 10–50 mm2 50 5.7 VC-6 0.265 6.7 VC250KA3 1 KA, KH, KC, KI #4–#300 MCM 25–150 mm2 50 5.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Power Distribution Connectors Power distribution connectors can be used for multiple lead wire connections on one circuit breaker. Field installable kits, including aluminum alloy connectors and all necessary mounting hardware, are available for the Schneider Electric FA, KA, LA, Q4 and MA molded case circuit breakers. Each is UL Listed (per UL Standard 486a) for copper wire only.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Table 59: Rear Connecting Studs—Selection Data1 (continued) Dimensions Circuit Breaker Catalog Number Prefix KAL KHL LAL LHL LAL LHL MAL MHL MAL MHL 1 Ampere Ratings Stud Catalog Number in. (mm) Overall Length Back of Circuit Breaker Diameter Threads / in. 70–225 KAS–45 2.125 (53.98) 13.018 (330.66) 4.825 (122.56) 11.748 (298.40) 0.50 (12.7) 1.27 (32.26) 13 (330.2) 5.19 (131.83) 125–400 LAS–54 6.188 (157.18) 15.718 (399.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers LC, LI, LE, LX and LXI Circuit Breaker Termination Clip Kit The standard lugs supplied with LC and LI circuit breakers are secured by means of a screw fastened through the circuit breaker terminal into the lug body. If the standard lug is removed and a bolted connection to the circuit breaker terminal is desired, the AL600IN threaded terminal clip kit is required to make this connection.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Visi-blade Circuit Breakers Visi-blade construction is a modification to the cover of a thermal-magnetic circuit breaker, a molded case switch, or a Mag-Gard circuit breaker, which provides a window through which the position of the movable contacts can be verified. Luminescent paint is applied to the moveable contact arms to indicate their position. Visi-blade circuit breakers are UL Listed except for the FH.
Legacy Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers © 1991–2015 Schneider Electric All Rights Reserved 143 11/2015