North American Short Circuit and Motor Group Ratings
Model Overload Range Maximum RMS Short-Circuit Current, kA
240 V+ 480 V+ 600 V+
GP2E01 0.1-0.16 35 35 18
GP2E02 0.16-0.25 35 35 18
GP2E03 0.25-0.40 35 35 18
GP2E04 0.40-0.63 35 35 18
GP2E05 0.63-1.0 35 35 18
GP2E06 1.0-1.6 35 35 18
GP2E07 1.6-2.5 35 35 18
GP2E08 2.5-4.0 35 35 18
GP2E10 4.0-6.3 35 35 18
GP2E14 6-10 30 30 18
GP2E16 9-14 25 25 10
GP2E20 13-18 25 25 10
GP2E21 17-23 25 10 10
GP2E22 20-25 25 10 10
GP2E32 24-32 25 10 10
+ - Nominal System Voltage.
Easy TeSys contactors may be used on the load side of the Easy TeSys Manual
Motor Controllers in Group Installations on a circuit with an available short-circuit
current no greater than shown in the Table below when protected by fuses or circuit
breakers:
Type Contactor DPE Maximum RMS Short-Circuit Current, kA
480 Vac 600 Vac
GP2E01 DPE09 to DPE38 22 22
GP2E02 DPE09 to DPE38 22 22
GP2E03 DPE09 to DPE38 22 22
GP2E04 DPE09 to DPE38 22 22
GP2E05 DPE09 to DPE38 22 22
GP2E06 DPE09 to DPE38 22 22
GP2E07 DPE09 to DPE38 22 22
GP2E08 DPE09 to DPE38 22 22
GP2E10 DPE09 to DPE38 22 22
GP2E14 DPE12 to DPE38 22 22
GP2E16 DPE18 to DPE38 22 10
GP2E20 DPE18 to DPE38 22 10
GP2E21 DPE32 to DPE38 10 10
GP2E22 DPE32 to DPE38 10 10
* The above Group Installations may be used with Schneider’s GV2Gx45 or GV2Gx54 busbar,