Product Overview
B-2
Version 1.0 1st Feb. 2021
Easy TeSys catalog
Differential Thermal Overload Relays
for Use with Fuses or Circuit Breakers
■ Compensated relays with manual or automatic reset
■ with relay trip indicator
■ for a.c
Relay Setting
Range (A)
Fuses to Be Used
with Selected Relay
For Use with
Contactor
Reference Weight
Lb
aM (A) gG (A)
Class 10
(1)
for Connection by Screw Clamp Terminals
0.10…0.16 0.25 2 DPE09…32 DPER01 0.287
(0.13kg)
0.16…0.25 0.5 2 DPE09…32 DPER02 0.287
(0.13kg)
0.25…0.40 1 2 DPE09…32 DPER03 0.287
(0.13kg)
0.40…0.63 1 2 DPE09…32 DPER04 0.287
(0.13kg)
0.63…1 2 4 DPE09…32 DPER05 0.287
(0.13kg)
1…1.6 2 4 DPE09…32 DPER06 0.287
(0.13kg)
1.6…2.5 4 6 DPE09…32 DPER07 0.287
(0.13kg)
2.5…4 6 10 DPE09…32 DPER08 0.287
(0.13kg)
4…6 8 16 DPE09…32 DPER10 0.287
(0.13kg)
5.5…8 12 20 DPE09…32 DPER12 0.287
(0.13kg)
7…10 12 20 DPE09…32 DPER14 0.287
(0.13kg)
9…13 16 25 DPE12…32 DPER16 0.287
(0.13kg)
12…18 20 35 DPE18…32 DPER21 0.287
(0.13kg)
16…24 25 50 DPE25…32 DPER22 0.287
(0.13kg)
23…32 40 63 DPE25…32 DPER32 0.287
(0.13kg)
(1) Standard UL 60947-4-1 species a tripping time for 7.2 times the setting current I
R
:
class 10: between 4 and 10 seconds.
Characteristics
Easy TeSys thermal overload relays
3-pole thermal overload relays
Direct connection to Easy TeSys contactors