Product Overview
A-6
Version 1.0 1st Feb. 2021
Easy TeSys catalog
Easy TeSys contactors
Auxiliary contact blocks
Characteristics
Environment Characteristics
For Use in Normal Operating Environments
Type of Contact Block DPEAN
Conforming to standards IEC 60947-5-1, NF C 63-140, EN 60947-5-1, UL 60947-5-1 and CSA C22.2 No.60947-5-1
Product certications UL, CSA
Protective treatment Conforming to IEC 60068 “TH”
Degree of protection Conforming to VDE 0106 Protection against direct nger contact IP 2X
Ambient air temperature
around the device
Storage °F -76...176 (-60...80ºC)
Operation °F 23...140 (-5...60ºC)
Permissible for operation at Uc °F -40...158 (-40...70ºC)
Maximum operating altitude Without derating ft 6561.68 (2000m)
Connection by cable Philips n°2 and Ø 0.236 (6mm)
Flexible or rigid cable
with or without cable end
mm
2
Min: 1 x 1, max: 2 x 2.5
Characteristics of Instantaneous Contacts
Type of Contact Block DPEAN
Number of contacts 2
Rated operational voltage (Ue) Up to V 690
Rated insulation voltage (Ui) Conforming to IEC 60947-5-1 V 690
Conforming to UL, CSA V 600
Conventional
thermal current (Ith)
For ambient temperature ≤ 140ºF
(60ºC)
A 10
Frequency of the operational current Hz 25…400
Minimum switching capacity U min V 17
I min mA 5
Short-circuit protection Conforming to IEC 60947-5-1
and VDE 0660
gG fuse: 10 A
Rated making capacity Conforming to IEC 60947-5-1,
I rms
A a : 140, c : 250
Short-time rating Permissible for 1 s A 100
500 ms A 120
100 ms A 140
Insulation resistance mΩ > 10
Mechanical durability In millions of operating cycles 30