Technical Data Bulletin

Class 3100 Heavy Duty Safety Switches
Terminal Lug Data
Table 43 - Terminal Lug Data
Rating (A)
98
Wires Per
Phase and
Neutral
Wire Range Wire
Bending Space Per
NEC Table 312.6 AWG/
kcmil
Lug Wire Range AWG/
kcmil
Optional
99
Versa-
Crimp™ Compression
Lug Field-Installed
Optional Copper Only
Versa-Crimp™
Compression Lug
Field-Installed
99 100
30
1
12–6 (Al) or 14–6 (Cu)
12–2 (Al) or 14–2 (Cu)
C10–14
101
, D8–14,or
E6–14
2
12–10 (Al) or 14–10 (Cu)
60
102
1
12–3 (Al) or 14–3 (Cu) 12–2 (Al) or 14–2 (Cu)
C10–14
101
, D8–14, or
E6–14
100
103
1
12–1/0 (Al) or 14–1/0
(Cu)
12–1/0 (Al) or 14–1/0
(Cu)
VCEL02114S1 VCELC02114S1
200
104
1
6–250 (Al/Cu) 6–300 (Al/Cu)
VCEL030516H1 VCELC030516H1
400
105
1 or 2
1/0–750 (Al/Cu) or 1/0–
300 (Al/Cu)
1/0–750 (Al/Cu) and 1/
0–300 (Al/Cu)
VCEL07512H1
or
VCEL030516H1
106
and
VCEL05012H1
VCELC07512H1
or
VCELC030516H1
107
and
VCELC05012H1
600 2
3/0–500 (Al/Cu) 3/0–500 (Al/Cu)
VCEL05012H1 VCELC05012H1
800 3
3/0–750 (Al/Cu) 3/0–750 (Al/Cu)
H8LKE2
108
1200 4
3/0–750 (Al/Cu) 3/0–750 (Al/Cu)
H12LKE2
44 3100CT1602
98. 30–100 A switches suitable for 140°F (60°C) or 167°F (75°C) conductors. 200–1200 A switches suitable for 167°F (75°C) conductors.
99. Hubbell Versa-Crimp™ unless otherwise noted.
100. For NEMA Type 1, 12/3R, 12K and 4/4X/5 stainless steel switches only.
101. Order C10–14, D8–14 and E6–14 from Thomas and Betts.
102. H60XBD and H60XBDAA use 167°F (75°C) copper wire only. #6 AWG copper wire required for 60 A rating.
103. H100XBD and H100XBDAA use 167°F (75°C) copper wire only. #3 AWG copper wire required for 100 A rating.
104. H225XJG and H225XJGAA use 167°F (75°C) copper wire only. Lug wire range is #3 AWG 350 kcmil. Not UL Listed due to inadequate
wire bending space (5 in. (127 mm) on the ON end, 6 in. (152 mm) on the OFF end).
105. Maximum wire bending space allows for (1) 600 kcmil or (2) 300 kcmil Al/Cu on NEMA Type 4/4X/5 stainless steel and NEMA Type 12
switches.
106. For NEMA Type 1 and 3R only. For NEMA Type 4/4X/5 stainless steel and NEMA Type 12/3R, 12K use VCEL03038H1 (Al/Cu) or
VCELC03038H1 (Cu only). Order two PK516KN mounting kits when installing VCEL030516H1 lugs. Only one kit is required on two-pole
switches. PK561KN consists of four 5/16–18 (7 mm) Keps Nuts.
107. For NEMA Type 4/4X/5 stainless steel and NEMA Type 12/3R, 12K use VCEL03038H1 (Al/Cu) or VCELC03038H1 (Cu only). Order two
PK516KN mounting kits when installing VCEL030516H1 or VCELC030516H1 lugs. Only one kit is required on two-pole switches. PK561KN
consists of four 5/16–18 (7 mm) Keps Nuts.
108. For 800 and 1200 A compression lug kits, see Table 37 on page 35 for additional information.