Technical Data Bulletin

Class 3100 Heavy Duty Safety Switches
Crouse-Hinds Arktite™ Receptacle
H362WC Interlocked
Receptacle Switch
with Crouse-Hinds
Arktite Receptacle
UL Listed
Available in 30–100 A, 600 Vac / 250 Vdc, fused or non-fused, NEMA Type 1,
NEMA Type 4/4X/5 stainless steel and NEMA Type 12/3R
Suitable for use as service equipment
Receptacles are cast aluminum and copper free for NEMA Type 1 and NEMA
Type 12/3R safety switches.
Receptacles are epoxy powder coated and copper free cast aluminum for NEMA
Type 4/4X/5 stainless steel safety switches.
Table 23 - Crouse-Hinds Arktite Safety Switch Horsepower Ratings
Amperes
NEMA
Type 1
NEMA Type
4/4X/5 304
Stainless Steel
NEMA Type
12/3R
Use with
Plug
Horsepower Ratings—3Ø
Cat. No. Cat. No. Cat. No. Cat. No.
480 Vac
54
600 Vac
54
250 Vdc
55
Std. Max. Std. Max. Std. Max.
Fusible—3P, 600 Vac 250 Vdc
30 H361WC H361DSWC H361AWC APJ3485 5 15 7–1/2 20 5
60 H362WC H362DSWC H362AWC APJ6485 15 30 15 50 10
100 H363WC H363DSWC H363AWC APJ10487 25 60 30 75 20
Non-Fusible—3P, 600 Vac 250 Vdc
30 HU361WC HU361DSWC HU361AWC APJ3485
20
30
5
60 HU362WC HU362DSWC HU362AWC APJ6485
50
60
10
100 HU363WC HU363DSWC HU363AWC APJ10487
60
100
20
Table 24 - Crouse-Hinds 600 Vac Short Circuit Current Rating
Amperes
10 kAIR Fuses 100 kAIR Fuses 200 kAIR Fuses
14 kAIR Circuit
Breaker
18 kAIR Circuit
Breaker
Fusible—3P, 600 Vac 250 Vdc
30
H, K
J, R
60
H, K
J, R
100
H, K
J, R
Non-Fusible—3P, 600 Vac 250 Vdc
30
H, K J, R, T
56
J, R, T
FA FH
60
H, K
J, R, T
FA FH
100
H, K
J, R, T
FA FH
28 3100CT1602
54. Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses.
55. For switching dc, use two outside switching poles.
56. SCCR when using 60 A Max fuse.