Technical Data Bulletin

Heavy Duty Safety Switches Class 3100
Appleton Powertite™ Receptacle
H362AWA
Interlocked
Receptacle Switch
with Appleton
Powertite
Receptacle
UL Listed and CSA Certified
Available in 30–100 A, 600 Vac / 250 Vdc, fused or non-fused, NEMA Type 1,
NEMA Type 4/4X/5 stainless steel and NEMA Type 12/3R
Suitable for use as service equipment (USA only)
Receptacles are epoxy powder coated over copper-free cast aluminum
Table 21 - Appleton Powertite Receptacle Safety Switch Horsepower Ratings
Amperes
NEMA
Type 1
NEMA Type 3,
3R, 4, 4X, 5
and 12 304
Stainless
Steel
NEMA Type
12 and 3R
Use with
Plug
50
Horsepower Ratings—3Ø
Cat. No. Cat. No. Cat. No.
480 Vac
51
600 Vac
51
250 Vdc
52
Std. Max. Std. Max. Std. Max.
Fusible—3P, 600 Vac 250 Vdc
30 H361WA H361DSWA H361AWA ACP3034BC 5 15 7–1/2 20 5
60 H362WA H362DSWA H362AWA ACP6034BC 15 30 15 50 10
100 H363WA H363DSWA H363AWA ACP1034CD 25 60 30 75 20
Non-Fusible—3P, 600 Vac 250 Vdc
30 HU361WA HU361DSWA HU361AWA ACP3034BC
20
30
5
60 HU362WA HU362DSWA HU362AWA ACP6034BC
50
60
10
100 HU363WA HU363DSWA HU363AWA ACP1034CD
75
100
20
Table 22 - Appleton Powertite 600 Vac Short Circuit Current Rating
Amperes
10 kAIR Fuses 100 kAIR Fuses 200 kAIR Fuses
14 kAIR Circuit
Breaker
18 kAIR Circuit
Breaker
Fusible—3P, 600 Vac 250 Vdc
30
H, K
J, R
60
H, K
J, R
100
H, K
J, R
Non-Fusible—3P, 600 Vac 250 Vdc
30
H, K J, R, T
53
J, R, T
FA FH
60
H, K
J, R, T
FA FH
100
H, K
J, R, T
FA FH
3100CT1602 27
50. Receptacle UL listed for use with Appleton™ACP or CPH plugs; UL Classified for use with Crouse-Hinds APJ Arktite™plugs. See Appleton
Powertite Receptacle, page 27.
51. Std.—Using fast acting one time fuses. Max.—Using dual element time delay fuses.
52. For switching dc, use two outside switching poles.
53. SCCR when using 60 A Max fuse.