Technical Data Bulletin

Class 3100 Heavy Duty Safety Switches
Table 19 - Krydon 600 Vac Short Circuit Current Rating (Continued)
Catalog Number
10 kAIR Fuses 100 kAIR Fuses 200 kAIR Fuses
14 kAIR
Circuit Breaker
18 kAIR
Circuit Breaker
HU362DX
H, K J, R, T
43
J, R, T
FA FH
HU363DX
H, K J, R, T
44
J, R, T
FA FH
NEMA Type 7/9
H60XBD
An enclosed automatic molded case switch for use in divisions 1 and 2 of the
following: Class I, Group C and D; Class II, Groups E, F and G; or Class III,
Hazardous Locations as defined in the NEC Article 500.
cULus Listed
Suitable for use as service equipment
“Raintight” for outdoor applications
Standard with threaded conduit opening in both top and bottom endwall
Standard with equipment grounding lugs installed (see Table 30 on page 30 for
terminal data)
Table 20 - NEMA Type 7/9, Three-Pole Molded Case Switch, 600 Vac, 250 Vdc For
switching dc, Short Circuit Current Rating 10 kA AIR
Amperes
Enclosed
Molded Case
Switch
45
Solid Neutral
Assembly
Horsepower Ratings—3Ø
46
Size of Threaded Conduit
Openings Provided
47
Cat. No. Cat. No. 240 Vac 480 Vac 600 Vac in.
mm
60 H60XBD 100SNA 15 30 50 3/4 19
60
H60XBDAA
48
100SNA 15 30 50 3/4 19
100 H100XBD 100SNA 30 60 75 1–1/4 31
100
H100XBDAA
48
100SNA 30 60 75 1–1/4 31
225
H225XJG
49
225SNA 60 125 150 2–1/2 63
225
H225XJGAA
48 49
225SNA 60 125 150 2–1/2 63
Receptacle Switches
Interlocked receptacle switches are furnished with a factory-installed, three-phase,
four-wire, Appleton Powertite
, Crouse-Hinds Style 2 Arktite
or Hubbellock™
receptacle. The fourth wire is connected to the switch equipment grounding terminal
and is not a solid neutral termination. Interlocking linkage between the receptacle and
switch mechanism prevents insertion or removal of the plug while the switch is in the
“ON’’ position or insertion of any plug other than specified. The interlocking
mechanism also prevents the switch from being turned “ON” if a plug has not been
fully inserted into the receptacle.
26 3100CT1602
43. SCCR 100 kAIR when protected by R, J or T fuses rated 100 A maximum.
44. SCCR 100 kAIR when protected by R, J or T fuses rated 200 A maximum.
45. Includes PKDB1, breather and drain kit, required for rainproof application.
46. For switching dc, see PowerPact B or PowerPact J catalog for Vdc wiring details. Not for use on dc motor applications.
47. Threaded conduit opening provided in top and bottom endwall.
48. Includes 1NO/1NC auxiliary contacts.
49. Not cULus listed due to wire bending space.