Altivar Machine ATV320 QGH39563 02/2017 Altivar Machine ATV320 Variable Speed Drives for Asynchronous and Synchronous Motors ATV312 to ATV320 Migration Manual QGH39563.01 02/2017 www.schneider-electric.
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Table of Contents Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chapter 1 Introduction to Device Conversion Function . . . . . . . . . . . . . . . . . . . . . . . . Device Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chapter 2 Control Block Terminals . . . . . . .
QGH39563 02/2017
Safety Information Important Information NOTICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
Intended Use This product is a drive for three-phase synchronous and asynchronous motors and intended for industrial use according to this manual.The product may only be used in compliance with all applicable safety regulations and directives, the specified requirements and the technical data.Prior to using the product, you must perform a risk assessment in view of the planned application. Based on the results, the appropriate safety measures must be implemented.
Damaged products or accessories may cause electric shock or unanticipated equipment operation. DANGER ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION Do not use damaged products or accessories. Failure to follow these instructions will result in death or serious injury. Contact your local Schneider Electric sales office if you detect any damage whatsoever.
QGH39563 02/2017
About the Book At a Glance Document Scope The document provides the information about migration from ATV312 to ATV320. Validity Note This documentation is valid for ATV320 devices which support device conversion. The technical characteristics of the devices described in this document also appear online. To access this information online: Step Action 1 Go to the Schneider Electric home page www.schneider-electric.com. 2 In the Search box type the reference of a product or the name of a product range.
Related Documents Use your tablet or your PC to quickly access detailed and comprehensive information on all our products on www.schneider-electric.
Terminology The technical terms, terminology, and the corresponding descriptions in this manual normally use the terms or definitions in the relevant standards. In the area of drive systems this includes, but is not limited to, terms such as error, error message, failure, fault, fault reset, protection, safe state, safety function, warning, warning message, and so on. Among others, these standards include: IEC 61800 series: Adjustable speed electrical power drive systems IEC 61508 Ed.
QGH39563 02/2017
Altivar Machine ATV320 Introduction to Device Conversion Function QGH39563 02/2017 Chapter 1 Introduction to Device Conversion Function Introduction to Device Conversion Function Device Conversion Overview Device conversion allows you to convert the configuration (.psx file) of one device (source device) to another device (target device). For example: The ATV312 configuration can be used as ATV320 configuration after the device conversion operation.
Introduction to Device Conversion Function Conversion of Device Configuration The table provides the procedure to convert the device configuration Step 1 Action Comments On the SoMove start page, do one of the following Click the Device Conversion button Press CTRL + ALT + Q keys, on the menu bar, click File →Device Conversion Result: Opens Device Conversion dialog box NOTE: 2 The Source zone displays the path and the device type of selected configuration.
Altivar Machine ATV320 Control Block Terminals QGH39563 02/2017 Chapter 2 Control Block Terminals Control Block Terminals What Is in This Chapter? This chapter contains the following topics: Topic QGH39563 02/2017 Page Control Terminals 16 Digital Inputs 18 Digital Outputs 19 Analog Inputs 20 Analog Outputs 20 Power Supplies 21 Relays 21 15
Control Block Terminals Control Terminals Introduction ATV320 offers similar control terminals as ATV312. Below is the presentation of terminals of each product.
Control Block Terminals ATV312 and ATV320 Inputs/Outputs Description The table provides the list of inputs and outputs available on ATV312 and ATV320 drives ATV312 ATV320 Description LI1 DI1 Digital inputs LI2 DI2 LI3 DI3 LI4 DI4 LI5 DI5 LI6 DI6 CLI – SW SW1 Digital input switch DQ+, DQ- Digital output AI1 AI1 Analog input 1 AI2 AI2 Analog input 2 AI3 AI3 Analog input 3 AOV AQ1 Analog output voltage AOC – Analog output current AOC (1) 10 V 10 V Internal supply for
Control Block Terminals Digital Inputs Characteristics The table provides the characteristics of digital inputs of ATV312 and ATV320 devices Digital Inputs Characteristics ATV312 ATV312 ATV320 Programmable logic inputs Programmable digital inputs configurable as sink or source using SW1 switch + 24 Vdc power supply (max.
Control Block Terminals Digital Outputs Characteristics The table provides the characteristics of digital outputs of ATV312 and ATV320 devices Digital Outputs Characteristics ATV312 ATV320 ATV312 AOC DQ+, DQ- Can be configured as 24 Vdc logic output Open collector output configurable as sink or on AOC, min. load impedance 1.2 kΩ source using SW1 switch.
Control Block Terminals Analog Inputs Characteristics The table provides the characteristics of analog inputs of ATV312 and ATV320 devices Analog Inputs Characteristics ATV312 ATV320 ATV312 ATV320 AI1 AI1 Analog input 0 + 10 Vdc Analog input 0 + 10 Vdc Impedance 30 kΩ Resolution: 10-bit converter Accuracy ± 0.5%, Linearity ± 0.2% of max. value Sampling time 2 ms Impedance 30 kΩ Resolution: 10-bit converter Precision ± 4.3%, linearity ± 0.2%, of max.
Control Block Terminals Power Supplies Characteristics The table provides the characteristics of power supplies of ATV312 and ATV320 devices Power supplies Characteristics ATV312 ATV320 ATV312 10 V 10 V +10 Vdc (+ 8 - 0%), 10 mA max, protected Internal supply for the analog inputs against short-circuits and overloads Tolerance ± 10% Current: maximum 10 mA 24 V +24 V + 24 Vdc protected against short-circuits +24 Vdc input supply and overloads, min. 19 Vdc, max. 30 Vdc Tolerance: -15...
Control Block Terminals 22 QGH39563 02/2017
Altivar Machine ATV320 Function Compatibilities QGH39563 02/2017 Chapter 3 Functions Compatibilities Functions Compatibilities What Is in This Chapter? This chapter contains the following topics: Topic 24 Reverse 26 Reverse Inhibition 26 Speed Loop Parameters 26 Macro-Configurations 27 I/O Multi-Assignments 27 2/3 Wires Control 27 Freewheel Stop 28 Fast Stop 28 Ramp Types 28 Ramp Switching 29 Ramp Auto-Adaptation 29 DC Injection Braking 29 Reference Switching 30 Separate Mode (
Function Compatibilities Applicative Functions Introduction ATV320 offers similar applicative functions compare to ATV312. ATV320 offers also additional functions like functional safety, ATV Logic, and so on For more information about the ATV320 functions, refer to the ATV320 Programming Manual (NVE41295). WARNING UNANTICIPATED EQUIPMENT OPERATION Device conversion function is used to apply the configuration from a drive product range to another drive product range.
Function Compatibilities Function QGH39563 02/2017 ATV312 ATV320 Conversion PID regulator ✓ ✓ No Internal PID reference ✓ ✓ No Preset PID reference ✓ ✓ No PID predictive speed – ✓ – Sleep / WakeUp ✓ ✓ No Catch on the fly ✓ ✓ Yes Automatic restart ✓ ✓ Yes Limit switches ✓ ✓ No Positioning – ✓ – Supply Mains contactor control – ✓ – Output contactor control – ✓ – Traverse control – ✓ – Parameter sets switching – ✓ – Multi-Motors, Multi-Configurations ✓
Function Compatibilities Reverse Overview This function is available in both ATV312 and ATV320 drives In factory settings, the reverse function [Reverse Assign] RRS is set to the [DI2] LI2 on both products. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is supported for this function.
Function Compatibilities Macro-Configurations Overview This function is available in both ATV312 and ATV320 drives but macro-configuration lists are not the same. On ATV312, there are 2 sets of macro configurations. On ATV320, there are 6 sets of macro configurations. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is not supported for this function.
Function Compatibilities Freewheel Stop Overview This function is available in both ATV312 and ATV320 drives. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is supported for this function. For more information about Freewheel Stop, refer to the ATV320 Programming Manual (NVE41295). Fast Stop Overview This function is available in both ATV312 and ATV320 drives.
Function Compatibilities Ramp Switching Overview This function is available in both ATV312 and ATV320 drives. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is supported for this function. The parameters related to this function are set to factory setting values and needs to be adjusted depending on the application. For more information about Ramp Switching, refer to the ATV320 Programming Manual (NVE41295).
Function Compatibilities Reference Switching Overview This function is available in both ATV312 and ATV320 drives but configuration of this function is not the same. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is not supported for this function. For more information about Reference Switching, refer to the ATV320 Programming Manual (NVE41295).
Function Compatibilities Jog Overview This function is available in both ATV312 and ATV320 drives. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is supported for this function. For more information about Jog, refer to the ATV320 Programming Manual (NVE41295). Preset Speeds Overview This function is available in both ATV312 and ATV320 drives. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is supported for this function.
Function Compatibilities 2nd Current Limitation Overview This function is available in both ATV312 and ATV320 drives. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is supported for this function. For more information about 2nd Current Limitation, refer to the ATV320 Programming Manual (NVE41295). Jump Frequency Overview This function is available in both ATV312 and ATV320 drives. ATV320 offers additional parameters for this function.
Function Compatibilities Preset PID Reference Overview This function is available in both ATV312 and ATV320 drives but configuration of this function is not the same. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is not supported for this function. The parameters related to this function are set to factory setting values and needs to be adjusted depending on the application.
Function Compatibilities Multi-Motors / Multi-Configurations Overview This function is available in both ATV312 and ATV320 drives but configuration of this function is not the same. Device Conversion Conversion from an ATV312 configuration into ATV320 configuration is not supported for this function. The parameters related to this function are set to factory setting values and needs to be adjusted depending on the application.
ATV312_to_ATV320_Migration_Manual_EN_QGH39563_01 02/2017