Brochure
© 2019 Schneider Electric
All Rights Reserved
26-27
schneider-electric.us
S–Flex
TM
212 AC Drives Enclosed Building Drives Selection Tables
Panel Mounted / Open AC Drive Solutions
S-Flex™ Variable Torque AC Drive—208 V, 230 V, and 460 V
Ratings
S-Flex 212 Enclosed
Drive Controller Type 1, 12, 3R
Rated +14 to +104 °F
(-10 to +40 °C)
M
AFC
Power
Circuit Y
M
AFC
Power
Circuit W
The AHRI certified S-Flex enclosed drive features the Altivar 212 drive and provides
100 KAIC rating for commercial pump, fan, and scroll compressor applications.
The S-Flex is an economical package that includes a circuit breaker disconnect and
option bypass contactors, drive input disconnect switch or line contactor.
The S-Flex is rated as a UL Type 1, 12, and 3R enclosure an ideal for use in residential
high rise and mixed-use buildings, commercial office buildings, schools and campus
environments.
All S-Flex 212 Enclosed Drives are supplied with:
•
Altivar™ 212 power converter
•
Square D™ circuit breaker disconnect (Power Fuses for
460 V version only)
•
Coordinated short circuit rating for 100,000 A
•
Adjustable Frequency Controller-Off-Bypass selector
switch
•
Local/Remote configurable on controller
•
Power On red LED
•
Bypass Run green LED
•
Fire/Freezestat interlock for Adjustable Frequency Drive
and Bypass mode
•
Form C Adjustable Frequency Controller fault
auxiliary contact
•
Modbus RJ-45 communication port
•
Smoke Purge Function
•
Bypass Run Auxiliary Contact
•
Drive Run Auxiliary Contact
•
Full Voltage Bypass Power Circuit with overload
relay
•
120 Vac fused control power transformer
Table 26.23: Output Amperes
HP 208 V 230 V 460 V
1 4.8 4.2 2.1
2 7.8 6.8 3.4
3 11 9.6 4.8
5 17.5 15.2 7.6
7.5 25.3 22 11
10 32.2 28 14
15 48.3 42 21
20 62.1 54 27
25 78.2 68 34
30 92 80 40
40 120 104 52
50 — — 65
60 — — 77
75 — — 96
100 — — 124
Table 26.24: S-Flex 212 Type 1 Enclosed Drive Controller Selection
Input Line
Voltage
HP kW
Output Current
Catalog
Number
A
208 Vac
Three-phase
1 0.75 4.8 SFD212CG2YB07D07
2 1.5 7.8 SFD212DG2YB07D07
3 2.2 11 SFD212EG2YB07D07
5 4 17.5 SFD212FG2YB07D07
7.5 5.5 25.3 SFD212GG2YB07D07
10 7.5 32.2 SFD212HG2YB07D07
15 11 48.3 SFD212JG2YB07D07
20 15 62.1 SFD212KG2YB07D07
25 18.5 78.2 SFD212LG2YB07D07
30 22 92 SFD212MG2YB07D07
40 30 120 SFD212NG2YB07D07
460 Vac
Three-phase
1 0.75 2.1 SFD212CG4YB07D07
2 1.5 3.4 SFD212DG4YB07D07
3 2.2 4.8 SFD212EG4YB07D07
5 4 7.6 SFD212FG4YB07D07
7.5 5.5 11 SFD212GG4YB07D07
10 7.5 14 SFD212HG4YB07D07
15 11 21 SFD212JG4YB07D07
20 15 27 SFD212KG4YB07D07
25 18.5 34 SFD212LG4YB07D07
30 22 40 SFD212MG4YB07D07
40 30 52 SFD212NG4YB07D07
50 37 65 SFD212PG4YB07D07
60 45 77
SFD212QG4YB07D07
75 55 96 SFD212RG4YB07D07
100 75 124 SFD212SG4YB07D07
Table 26.25: Additional S-Flex Configurations Available Using Product Selector
Example:SFD212CG3YA06X07 (bold text in selection table below)
TYPE (01) HP (02) Enclosure (03) Voltage (04) Power Circuit (05) Communication Options (06) Misc Options (07)
SFD212
C = 1 hp
D = 2 hp
E = 3 hp
F = 5 hp
G = 7.5 hp
H = 10 hp
J = 20 hp
K= 20 hp
L = 30 hp
N = 40 hp
P = 50 hp (460 V only)
Q = 60 hp (460 V only)
R = 75 hp (460 V only)
S = 100 hp (460 V only)
G = UL Type 1
General Purpose
A = UL Type 12K
Industrial Use,
Dust-Tight/Drip-
Tight
H = UL Type 3R
Outdoor Use
2 = 208 Vac
3 = 230 Vac
4 = 460 Vac
W = Without Bypass
Y = Full Voltage Bypass
A06 = BACnet Setup
B06 = LonWorks® Card
C06 = Metasys® N2 Setup
D06 = Apogee™ P1 Setup
N06 = Modbus [1]
A07 = Drive Input Disconnect [2]
B07 = Line Contactor [2]
S07 = Seismic Certification
D07 = Full Text Keypad
K07 = cUL Marking (Canada)
T07 = 50 °C Ambient Operation[3]
X07 = AC Line Reactor
Table 26.26: S-Flex Accessories
Description Catalog Number
Software
SoMove™
This software enables the user to configure, set, debug and organize maintenance task for the complete Altivar product line and the Altistart 22 and Altistart 48
soft starters. It can also be used to customize the integrated display terminal menus. It can be used with a direct connection or a Bluetooth® wireless
connection. Free download www.schneider-electric.us
User Interface Kits
USB to RJ45 Adaptor Kit (For use in connecting to a PC with a USB port)
TCSMCNAM3M002P
EZ-M Mounting Channel, 72 in. length
EZM72MC
Altivar and Altistart Programming cable for iPad 30–Pin mobile to RS-485 Converter, 2 meters
VW3A8151R20U
NOTE: See the Instruction Bulletin for set up instructions.
26
AC DRIVES AND SOFT STARTERS
[1] Default selection. For Modbus control, see the Instruction manual.
[2] Options A07 Drive Input disconnect and B07 line contactor are available only when a full voltage bypass option Y is selected. Options A07 and B07 are mutually exclusive.
[3] For UL Type 12 and 3R only.