(a) The Altivar 212 has a 100k SCC rating on the output of the drive as many other drives are rated. In addition to providing a rating based on
shorting the output of the drive, these short circuit rating have been obtained by testing the weakest point internal to the ATV212 per UL508C.
These ratings allow proper coordination of short circuit protection. The amp rating of the short circuit protection devices in the table are maximum
values. Smaller amp sizes may be used.
(b) Ratings also apply to ATV212 Type 1 product, ie: an ATV212 fitted with a conduit box.
(c) Ratings apply to an ATV212 mounted in a non-ventilated Type 1, 3R, 4(X) or 12 rated enclosure. Minimum enclosure volume is 3.375 times
the drive volume.
(d) 480 V ratings are for Wye connected electrical distribution systems. GV2Ppp self protected manual combination starter must be used with
GV2GH7 insulating barrier to meet UL 508 Type E rating
(e) Fuse type can be fast acting or time delay, or Class CC.