74 EAV64301 03/2019
Scheduled Servicing
Servicing
The temperature of the products described in this manual may exceed 80 °C (176 °F) during operation.
Adherence to the environmental conditions must be ensured during operation of the drive. In addition, during
maintenance, verify and, if appropriate, correct all factors that may have an impact on the environmental
conditions.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Read and understand the instructions in Safety Information chapter before performing any procedure in this
chapter.
Failure to follow these instructions will result in death or serious injury.
WARNING
HOT SURFACES
Ensure that any contact with hot surfaces is avoided.
Do not allow flammable or heat-sensitive parts in the immediate vicinity of hot surfaces.
Verify that the product has sufficiently cooled down before handling it.
Verify that the heat dissipation is sufficient by performing a test run under maximum load conditions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
INSUFFICIENT MAINTENANCE
Verify that the maintenance activities described below are performed at the specified intervals.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Part concerned Activity Interval (1)
Overall condition All parts such as housing, HMI,
control block, connections, etc.
Perform a visual inspection At least every year
Corrosion Terminals, connectors, screws,
EMC plate
Inspect and clean if required
Dust Terminals, fans, cabinet air inlets
and air outlets, air filters of cabinet
Inspect and clean if required
Drives filter mats Floor standing Inspect At least every year
Change At least every 4 years
Cooling Wall mounting drives fan Verify the fan operation At least every year
Replace the fan, see catalog and
the instructions sheets on
www.se.com
.
After 3 to 5 years, depending
on the operating conditions
Floor standing drives fan for power
part and enclosure door fan
Replace the fans, see catalog and
the instructions sheets on
www.schneider-electric.com.
Every 35000 operating hours
or every 6 years
Fastening All screws for electrical and
mechanical connections
Verify tightening torques At least every year
(1) Maximum maintenance intervals from the date of commissioning. Reduce the intervals between maintenance to adapt
maintenance to the environmental conditions, the operating conditions of the drive, and to any other factor that may
influence the operation and/ or maintenance requirements of the drive.