72 S1A53832 03/2019
Electrical installation
Verify the electrical connections and the cabling:
Covers And Seals
Verify that all devices, doors and covers of cabinet are properly installed to meet the required degree of
protection.
Recommended branch circuit protection devices
Please refer to the ATV212 Quick Start Annex document, reference S1A73476: Short Circuit Current Ratings
(SCCR) and branch circuit protection.
This document is delivered with the product, and you can download it on
www.se.com.
Step Action ✔
1 Did you connect all protective ground conductors?
2 The correct tightening of the screws may be altered during assembly and wiring phases of the drive.
Verify and adjust the tightening of all terminal screws to the specified nominal torque.
3 Do all fuses and circuit breaker have the correct rating; are the fuses of the specified type? in the Altivar
Process ATV212 Quick Start guide Annex (SCCR) catalog number: S1A73476 for UL/CSA compliance
and also in the catalog (see page
10
) for IEC compliance.
4 Did you connect or insulate all wires at the cable ends?
5 Did you properly connect and install all cables and connectors?
6 Do all plug-in terminals colors and markings correspond to the colors and marking of the control block?
7 Did you properly connect the signal wires?
8 Are the required shield connections EMC-compliant?
9 Did you take all measures for EMC compliance?
10 On floor standing products, verify that internal circuit breaker is closed