Install Instructions

62 S1A53832 03/2019
Characteristics
Terminals Function Characteristics
Default
function setting
PLC
External power
supply input
+24 Vdc input for external power supply for logic inputs
Max. permissible voltage: 50 Vdc
P24 Internal supply
Short-circuit and overload protection:
24 Vdc supply (min. 21 Vdc, max. 27 Vdc), maximum current: 200 mA
CC Common 0 Vdc common (2 terminals)
FLA,
FLB,
FLC
Configurable
relay outputs
1 relay logic output, 1 N/C contact, and 1 N/O contact with common point
Minimum switching capacity: 10 mA for 5 Vdc
Maximum switching capacity:
On resistive load (cos = 1): 5 A for 250 Vac or 30 Vdc
On inductive load (cos = 0.4 and L/R = 7 ms): 2 A for 250 Vac or
30 Vdc
Max. response time: 10 ms
Fault relay
RYA, RYC
1 relay logic output, 1 N/O contact
Minimum switching capacity: 3 mA for 24 Vdc
Maximum switching capacity:
On resistive load (cos = 1): 3 A for 250 Vac or 30 Vdc
On inductive load (cos = 0.4 and L/R = 7 ms): 2 A for 250 Vac or 30
Vdc
Max. response time: 7 ms ± 0.5 ms
Speed attained
F
R
RES
Configurable
logic inputs
3 programmable logic inputs, 24 Vdc, compatible with level 1 PLC,
IEC 65A-68 standard
Impedance: 4.7 k
Maximum voltage: 30 Vdc
Max. sampling time: 2 ms ±0.5 ms
Multiple assignment makes it possible to configure several functions on one
input
F: Run forward
(2-wire control)
R: Preset speed 1
command
(15 Hz)
RES: Clear trip
Positive logic (Source): State 0 if y 5 Vdc or logic input not wired,
state 1 if u 11 Vdc
Negative logic (Sink): State 0 if u 16 Vdc or logic input not wired,
state 1 if y 10 Vdc
FM
Configurable
analog output
1 switch-configurable (SW101) voltage or current analog output:
Voltage analog output 0–10 Vdc, minimum load impedance 7.62 k
Current analog output X–Y mA by programming X and Y from 0 to 20
mA, maximum load impedance: 970
Max. sampling time: 2 ms ±0.5 ms
Resolution: 10 bits
Accuracy: ±1 % for a temperature variation of 60 °C
Linearity: ±0.2%
Output
frequency
PP
Internal supply
available
Short-circuit and overload protection:
One 10.5 Vdc ± 5% supply for the reference potentiometer (1 to 10 k),
maximum current: 10 mA
VIA
Configurable
analog/logic input
Switch-configurable voltage or current analog input:
Voltage analog input 0–10 Vdc, impedance 30 k
maximum voltage: 24 Vdc
Analog current input X–Y mA by programming X and Y from 0
to 20 mA, with impedance 250
Max. sampling time: 3.5 ms ±0.5 ms
Resolution: 10 bits
Accuracy: ±0.6% for a temperature variation of 60 °C
Linearity: ±0.29% of the maximum value
This analog input is also configurable as a logic input.
Consult the Altivar 212 Programming Manual for more information.
Primary speed
reference,
0–10 V
VIB
Configurable
analog input
Voltage analog input, configurable as an analog input or as a PTC probe
input. Voltage analog input:
0–10 Vdc, impedance 30 k max. voltage 24 Vdc
Max. sampling time: 22 ms ±0.5 ms
Resolution: 10 bits
Accuracy: ±0.6% for a temperature variation of 60 °C
Linearity: ±0.29% of the maximum value
PTC probe input:
6 probes max. mounted in series
Nominal value < 1.5 k
Trip resistance 3 k, reset value 1.8 k
Short-circuit detection threshold < 50
Secondary speed
reference,
1–10 V
RJ45
Graphic display
terminal or
Modbus
Used to connect graphic display terminal or connect the drive to a Modbus
fieldbus.
Note: For using Modbus on the RJ45, modify parameter F807. See
Modbus manual.
Open Style
connector
Fieldbus Refer to communication manual related to the fieldbus.