Install Instructions
Table Of Contents
- Table of Contents
- Safety Information
- About the Book
- Before You Begin
- Steps for Setting Up
- Upstream Protective Device
- Technical Data
- Installation
- Drive mounting generalities
- Specific recommendations for mounting in an enclosure
- Position of the charging LED
- Opening the drive to access terminals
- Wiring recommendations
- Power terminals
- Control terminals and switches
- Installing option card
- Use on an impedance grounded (IT) system
- Electromagnetic compatibility (EMC)
- Checking the Installation
- Recommended branch circuit protection devices
- Maintenance
- Migration ATV21 --> ATV212
S1A53832 03/2019 55
Power terminals
ATV212H - Arrangement and characteristics of the power terminals
Connect the power terminals before connecting the control terminals.
ATV212H Maximum
wire size
Tightening
torque
(1)
mm
2
AWG
N·m
(lb-in)
075M3X,
U15M3X,
U22M3X,
U30M3X,
U40M3X
075N4, U15N4,
U22N4, U30N4,
U40N4
610
1.3
(11.5)
(1) On drives ATV212H075M3X...U55N4 first
remove control board to access power
terminals.
ATV212H Maximum wire
size
Tightening
torque
(1)
mm
2
AWG
N·m
(lb-in)
U55N4 610
1.3
(11.5)
U55M3X,
U75M3X
U75N4
D11N4
16 6
2.5
(22.0)
ATV212H Maximum wire
size
Tightening
torque
mm
2
AWG
N·m
(lb-in)
D11M3X,
D15M3X,
D18M3X
D15N4, D18N4,
D22N4S
25 3
4.5
(40.0)
A
B
Each power terminal has the structure shown in the figure at left. Connect a cable to
A if it has a ring terminal or to B if it does not have a terminal (bare wire).
Parts A and B can accommodate different cable sizes.
R/L1 S/L2 T/L3
P0 PA/+ PB PC/- U/T1 V/T2 W/T3
Ground screw
R/L1 S/L2 T/L3 P0 PA/+ PB PC/- U/T1 V/T2 W/T3
Ground
screw
R/L1 S/L2 T/L3 P0 PA/+ PB PC/- U/T1 V/T2 W/T3
Ground
screw