Specific recommendations for mounting in an enclosure
Note: The following only applies to ATV212HpppM3X and ATV212HpppN4 drives.
Minimum air flow rates
If you are installing the drive in a Type 1 enclosure, provide forced ventilation at a rate at least equal to the value
listed below each drive.
Sealed metal enclosure
The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as
dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.
This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.
When mounting the drive inside an UL Type 12 or IP54 enclosure, follow these ventilation instructions:
Observe the minimum clearance distances shown on page 40.
If necessary, install a stirring fan to circulate the air inside the enclosure, to help prevent hot spots in the drive,
and to distribute the heat uniformly to surfaces used for convection cooling.
Observe the mounting recommendations de-
scribed on page 40.
To help ensure proper air circulation in the drive:
Fit ventilation grilles.
Check that there is sufficient ventilation. If there is not, install a forced
ventilation unit with a filter. The openings and/or fans must provide a
flow rate at least equal to that of the drive fans (see below).
Use special filters with UL Type 12/IP54 protection.
Remove the blanking cover from the top of the drive, see page 41.
For drive Flow rate For drive Flow rate
m
3
/hour ft
3
/min m
3
/hour ft
3
/min
ATV212H075M3X 22 13 ATV212H075N4 19 12
ATV212HU15M3X 35 21 ATV212HU15N4 27 16
ATV212HU22M3X 41 25 ATV212HU22N4 35 21
ATV212HU30M3X 50 30 ATV212HU30N4 47 28
ATV212HU40M3X 66 39 ATV212HU40N4 60 36
ATV212HU55M3X 85 50 ATV212HU55N4 74 44
ATV212HU75M3X 118 70 ATV212HU75N4 100 59
ATV212HD11M3X 157 93 ATV212HD11N4 147 87
ATV212HD15M3X 215 127 ATV212HD15N4 206 122
ATV212HD18M3X 239 141 ATV212HD18N4 214 126
ATV212HD22M3X 261 154 ATV212HD22N4S 214 126
ATV212HD30M3X 371 219 ATV212HD22N4 214 126
ATV212HD30N4 290 171
ATV212HD37N4 334 197
ATV212HD45N4 429 252
ATV212HD55N4 498 293
ATV212HD75N4 666 392
NOTICE
RISK DUE TO CONDENSATION
Where condensation is possible, keep the drive powered up when the motor is not running, or install
thermostatically controlled strip heaters.
Failure to follow these instructions can result in equipment damage.