Install Instructions
Table Of Contents
- Table of Contents
- Safety Information
- About the Book
- Before You Begin
- Steps for Setting Up
- Upstream Protective Device
- Technical Data
- Installation
- Drive mounting generalities
- Specific recommendations for mounting in an enclosure
- Position of the charging LED
- Opening the drive to access terminals
- Wiring recommendations
- Power terminals
- Control terminals and switches
- Installing option card
- Use on an impedance grounded (IT) system
- Electromagnetic compatibility (EMC)
- Checking the Installation
- Recommended branch circuit protection devices
- Maintenance
- Migration ATV21 --> ATV212
42 S1A53832 03/2019
Removing the protective cover on ATV212H drives
See Mounting methods, page 41 to determine the type of mounting appropriate for your application before
removing the protective cover from the drive.
When IP20 protection is adequate, remove the protective cover on top of the drive as shown below.
For UL Type 1 protection, leave the protective cover on top of the drive and install a conduit entry kit (mounting
outside the enclosure). See entry kit references in the catalog on www.se.com.
Derating curves
The curves illustrate the drive nominal current derating percentage (I/In%) as a function of the temperature,
switching frequency, and the different types of mounting (A, B and C).
For example, 80% derating of a 20 hp, 460 V ATV212 drive nominally rated for 30.5 amperes continuously: 30.5
x 0.8 = 24.4 (15 hp).
For intermediate temperatures, interpolate between two curves.
ATV212H 075M3X to D18M3X, and
ATV212H 075N4 to D22N4S
ATV212H D22M3X to D30M3X and
ATV212H D22N4 to D30N4
ATV212H075M3X ATV212HU15M3X
ATV212HU22M3X ATV212HU30M3X, HU40M3X
30
40
50
60
70
80
90
In = 100
110
%
46
810
12
14
16
kHz
I / In
40 °C (104 °F) A, B, C
50 °C (122 °F) A, C
60 °C (140 °F) A, C
50 °C (122 °F) B
60 °C (140 °F) B
Switching frequency
30
40
50
60
70
80
90
In = 100
110
%
46
810
12
14
16
kHz
I / In
40 °C (104 °F) A, B, C
50 °C (122 °F) A, C
50 °C (122 °F) B
60 °C (140 °F) B
60 °C (140 °F) B
Switching frequency
30
40
50
60
70
80
90
In = 100
110
%
46
810
12
14
16
kHz
I / In
40 °C (104 °F) A, B, C
50 °C (122 °F) A, C
50 °C (122 °F) B
60 °C (140 °F) A, C
60 °C (140 °F) B
Switching frequency
30
40
50
60
70
80
90
In = 100
110
%
46
810
12
14
16
kHz
I / In
40 °C (104 °F) A, B, C
50 °C (122 °F) A, C
50 °C (122 °F) B
60 °C (140 °F) A, C
60 °C (140 °F) B
Switching frequency
Switching frequency
Switching frequency