Install Instructions
Table Of Contents
- Table of Contents
- Safety Information
- About the Book
- Before You Begin
- Steps for Setting Up
- Upstream Protective Device
- Technical Data
- Installation
- Drive mounting generalities
- Specific recommendations for mounting in an enclosure
- Position of the charging LED
- Opening the drive to access terminals
- Wiring recommendations
- Power terminals
- Control terminals and switches
- Installing option card
- Use on an impedance grounded (IT) system
- Electromagnetic compatibility (EMC)
- Checking the Installation
- Recommended branch circuit protection devices
- Maintenance
- Migration ATV21 --> ATV212
36 S1A53832 03/2019
ATV212Wppppp - Three-phase supply voltage: 380 ... 480 V 50/60 Hz
Drives with an integrated EMC filter, category C2, C3
ATV212Wppppp - Three-phase supply voltage: 380 ... 480 V 50/60 Hz
Drives with an integrated C1 EMC filter
(1) These values are given for a nominal switching frequency of 12 kHz up to ATV212WD15M3X and up to ATV212HD15N4
or 8 kHz for ATV212WD18M3X…HD30M3X and ATV212WD18N4…HD75N4 drives, for use in continuous operation at
40°C (104 °F) ambient.
Above 8 kHz or 12 kHz, depending on the rating, the drive will reduce the switching frequency automatically in the event of
an excessive temperature rise. For continuous operation above the nominal switching frequency, derate the nominal drive
current. See page 42 for derating curves as a function of switching frequency, ambient temperature, and mounting
conditions
(2) Current on a line supply with the "Input withstand rating", see QuickStart guide.
(3) Current on a line supply with the indicated short-circuit current rating.
(4) Note: The drive is designed to run up to 60 seconds at this level.
(5) See reference description on page 15.
Motor Line supply (input) Drive (output) Reference (5)
Power indicated
on plate (1)
Max. line current
(2)
Apparent
power
Max.
prospective
line Isc
(3)
Nominal
current
(1)
Max.
transient
current
(1) (4)
at 380 V at 480 V at 380 V
kW HP A A kVA kA A A
0.75 1 1.7 1.4 1.1 5 2.2 2.4 ATV212W075N4
1.5 2 3.2 2.5 2.1 5 3.7 4 ATV212WU15N4
2.2 3 4.6 3.6 3 5 5.1 5.6 ATV212WU22N4
3 3 6.2 4.9 4.1 5 7.2 7.9 ATV212WU30N4
4 5 8.1 6.4 5.3 5 9.1 10 ATV212WU40N4
5.5 7.5 10.9 8.6 7.2 22 12 13.2 ATV212WU55N4
7.5 10 14.7 11.7 9.7 22 16 17.6 ATV212WU75N4
11 15 21.2 16.9 14 22 22.5 24.8 ATV212WD11N4
15 20 28.4 22.6 18.7 22 30.5 33.6 ATV212WD15N4
18.5 25 34.9 27.8 23 22 37 40.7 ATV212WD18N4
22 30 41.6 33.1 27.3 22 43.5 47.9 ATV212WD22N4
30 40 56.7 44.7 37.3 22 58.5 64.4 ATV212WD30N4
37 50 68.9 54.4 45.3 22 79 86.9 ATV212WD37N4
45 60 83.8 65.9 55.2 22 94 103.4 ATV212WD45N4
55 75 102.7 89 67.6 22 116 127.6 ATV212WD55N4
75 100 141.8 111.3 93.3 22 160 176 ATV212WD75N4
Motor Line supply (input) Drive (output) Reference (5)
Power indicated
on plate (1)
Max. line current
(2)
Apparent
power
Max.
prospective
line Isc
(3)
Nominal
current
(1)
Max.
transient
current
(1) (4)
at 380 V at 480 V at 380 V
kW HP A A kVA A A A
0.75 1 1.7 1.4 1.1 5 2.2 2.4 ATV212W075N4C
1.5 2 3.2 2.6 2.1 5 3.7 4 ATV212WU15N4C
2.2 3 4.6 3.7 3 5 5.1 5.6 ATV212WU22N4C
3 3 6.2 5 4.1 5 7.2 7.9 ATV212WU30N4C
4 5 8.2 6.5 5.4 5 9.1 10 ATV212WU40N4C
5.5 7.5 11 8.7 7.2 22 12 13.2 ATV212WU55N4C
7.5 10 14.7 11.7 9.7 22 16 17.6 ATV212WU75N4C
11 15 21.1 16.7 13.9 22 22.5 24.8 ATV212WD11N4C
15 20 28.4 22.8 18.7 22 30.5 33.6 ATV212WD15N4C
18.5 25 34.5 27.6 22.7 22 37 40.7 ATV212WD18N4C
22 30 41.1 33.1 27.1 22 43.5 47.9 ATV212WD22N4C
30 40 58.2 44.4 38.3 22 58.5 64.4 ATV212WD30N4C
37 50 68.9 54.4 45.3 22 79 86.9 ATV212WD37N4C
45 60 83.8 65.9 55.2 22 94 103.4 ATV212WD45N4C
55 75 102.7 89 67.6 22 116 127.6 ATV212WD55N4C
75 100 141.8 111.3 93.3 22 160 176 ATV212WD75N4C