UL Circuit-Breakers and Fuses
Reference Document
UL Fuse and circuit-breaker information is provided in the ATV212 Quick Start guide Annex
(
S1A73476).
Complementary Information
The following table shows the minimum required prospective short-circuit current (Isc) depending on the drive
and associated circuit-breaker.
The following table shows the minimum required prospective short-circuit current (Isc) depending on the drive
and associated class J fuse, according to UL248-8.
Catalog Number PowerPact
Circuit-breakers
Minimum Isc
200...240 Vac 380...500 Vac (A)
ATV212U07M3X, ATV212U15M3X ATV212•075N4(C) H•L36015 1500
– ATV212•U15N4(C), ATV212•U22N4(C) H•L36015 1500
ATV212U22M3X ATV212•U30N4(C), ATV212•U40N4(C) H•L36020 1500
– ATV212•U55N4(C) H•L36025 1500
ATV212U30M3X ATV212•U75N4(C) H•L36030 1500
ATV212U40M3X – H•L36035 1700
ATV212U55M3X ATV212•D11N4(C) H•L36045 1700
ATV212U75M3X ATV212•D15N4(C) H•L36060 3000
– ATV212•D18N4(C) H•L36070 3000
ATV212D11M3X ATV212•D22N4(C)(S) H•L36090 3000
ATV212D15M3X ATV212•D30N4(C), ATV212•D37N4(C) H•L36125 3500
ATV212D18M3X ATV212•D45N4(C) H•L36150 3500
ATV212D22M3X ATV212•D55N4(C) H•L36175 3500
ATV212D30M3X ATV212•D75N4(C) H•L36225 4500
Catalog Number Class J Fuse
to UL248-8
Minimum Isc
200...240 Vac 380...500 Vac (A) (A)
– ATV212•075N4(C) 5 300
– ATV212•U15N4(C) 7.5 500
ATV212U07M3X ATV212•U22N4(C) 10 500
ATV212U15M3X ATV212•U30N4(C), ATV212•U40N4(C) 15 500
– ATV212•U55N4(C) 20 500
ATV212U22M3X ATV212•U75N4(C) 30 1000
ATV212U30M3X, ATV212U40M3X – 35 1500
ATV212U55M3X ATV212•D11N4(C) 45 2000
ATV212U75M3X ATV212•D15N4(C) 60 2000
– ATV212•D18N4(C) 80 2000
ATV212D11M3X ATV212•D22N4(C) 90 2500
ATV212D15M3X ATV212•D30N4(C) 110 2500
– ATV212•D37N4(C) 125 3000
ATV212D18M3X ATV212•D45N4(C) 150 3500
ATV212D22M3X – 175 5000
ATV212D30M3X ATV212•D55N4(C) 200 5000