Install Instructions

S1A53832 03/2019 27
IEC Fuses
Selection Table
Current limiting fuses can be chosen as SCPD according to the following table:
NOTE: Verify that the minimum Isc value above is lower than the value estimated in the Calculation section
(see page 24)
.
Catalog Number Fuse gG to IEC 60269-1 Fuse gR-aR to IEC 60269-4
Rating Minimum Isc Rating Minimum Isc
200...240 Vac 380...500 Vac (A) (A) (A) (A)
ATVATV212•075N4(C) 4 200 4 100
ATV212U07M3X ATV212•U15N4(C) 8 200 8 100
ATV212U15M3X ATV212•U22N4(C) 10 300 10 100
ATV212•U30N4(C) 12 300 12.5 200
ATV212U22M3X ATV212•U40N4(C) 16 400 16 200
ATV212U30M3X ATV212•U55N4(C) 20 1000 20 200
ATV212U40M3X ATV212•U75N4(C) 25 1000 25 300
32 2000 32 500
ATV212U55M3X ATV212•D11N4(C) 40 2000 40 500
ATV212U75M3X ATV212•D15N4(C) 50 2500 50 800
ATV212D11M3X ATV212•D18N4(C) 63 3000 63 1000
ATV212•D22N4(C) 80 4000 80 1500
ATV212D15M3X ATV212•D30N4(C) 100 5500 100 1500
ATV212D18M3X,
ATV212D22M3X
ATV212•D37N4(C) 125 6500 125 2000
ATV212D30M3X ATV212•D45N4(C),
ATV212•D55N4(C)
160 9000 160 2500
ATV212•D75N4(C),
ATV212•D90N4(C)
250 15000 250 5000