S1A53832 03/2019 27
IEC Fuses
Selection Table
Current limiting fuses can be chosen as SCPD according to the following table:
NOTE: Verify that the minimum Isc value above is lower than the value estimated in the Calculation section
(see page 24)
.
Catalog Number Fuse gG to IEC 60269-1 Fuse gR-aR to IEC 60269-4
Rating Minimum Isc Rating Minimum Isc
200...240 Vac 380...500 Vac (A) (A) (A) (A)
– ATVATV212•075N4(C) 4 200 4 100
ATV212U07M3X ATV212•U15N4(C) 8 200 8 100
ATV212U15M3X ATV212•U22N4(C) 10 300 10 100
– ATV212•U30N4(C) 12 300 12.5 200
ATV212U22M3X ATV212•U40N4(C) 16 400 16 200
ATV212U30M3X ATV212•U55N4(C) 20 1000 20 200
ATV212U40M3X ATV212•U75N4(C) 25 1000 25 300
– – 32 2000 32 500
ATV212U55M3X ATV212•D11N4(C) 40 2000 40 500
ATV212U75M3X ATV212•D15N4(C) 50 2500 50 800
ATV212D11M3X ATV212•D18N4(C) 63 3000 63 1000
– ATV212•D22N4(C) 80 4000 80 1500
ATV212D15M3X ATV212•D30N4(C) 100 5500 100 1500
ATV212D18M3X,
ATV212D22M3X
ATV212•D37N4(C) 125 6500 125 2000
ATV212D30M3X ATV212•D45N4(C),
ATV212•D55N4(C)
160 9000 160 2500
– ATV212•D75N4(C),
ATV212•D90N4(C)
250 15000 250 5000