IEC Type Circuit-Breaker as SCPD
Function
The circuit-breaker offers enhanced features versus fuse-link since it cumulates 3 functionalities:
insulation with lock,
switch (full load interruption),
downstream short-circuit protection without replacement.
Selection Table
Schneider Electric circuit-breaker, setting and limits shall be selected according to the following table:
NOTE: Verify that the minimum required prospective short-circuit current (Isc) value from the table above is lower
than the value estimated in the Calculation section
(see page 24)
.
Catalog Number Circuit-Breaker to IEC
60947-2
Ir m Minimum Isc
200...240 Vac 380...500 Vac (A) (A)
– ATV212•075N4(C) GV2L07 33.5 100
ATV212U07M3X ATV212•U15N4(C) GV2L08 51 100
ATV212U15M3X ATV212•U22N4(C)
ATV212•U30N4(C)
GV2L10 78 200
ATV212U22M3X ATV212•U40N4(C) GV2L14 138 300
ATV212U30M3X ATV212•U55N4(C) GV2L16 170 300
ATV212U40M3X ATV212•U75N4(C) GV2L20 223 400
ATV212U55M3X ATV212•D11N4(C) GV2L22 327 600
ATV212U75M3X ATV212•D15N4(C) GV3L32 448 700
– ATV212•D18N4(C) GV3L40 560 900
ATV212D11M3X ATV212•D22N4(C)(S) GV3L50 700 1100
ATV212D15M3X ATV212•D30N4(C) GV3L65 910 1800
– ATV212•D37N4(C) GV4L80 480 1800
ATV212D18M3X, ATV212D22M3X ATV212•D45N4(C) GV4L115 690 2500
ATV212D30M3X ATV212•D55N4(C) NSX160•MA150 1350 3200
– ATV212•D75N4(C) NSX250•MA220 1980 4700