Install Instructions
Table Of Contents
- Table of Contents
- Safety Information
- About the Book
- Before You Begin
- Steps for Setting Up
- Upstream Protective Device
- Technical Data
- Installation
- Drive mounting generalities
- Specific recommendations for mounting in an enclosure
- Position of the charging LED
- Opening the drive to access terminals
- Wiring recommendations
- Power terminals
- Control terminals and switches
- Installing option card
- Use on an impedance grounded (IT) system
- Electromagnetic compatibility (EMC)
- Checking the Installation
- Recommended branch circuit protection devices
- Maintenance
- Migration ATV21 --> ATV212
18 S1A53832 03/2019
Lifting and handling instructions
Storing and shipping
If the drive is not immediately installed, store it in a clean, dry area where the ambient temperature is between
–25 and +70 °C (–13 to +158 °F). If the drive has to be shipped to another location, use the original shipping
material and carton to help protect the drive.
WARNING
HANDLING AND LIFTING HAZARD
Keep the area below any equipment being lifted clear of all personnel and property. Use the lifting method
illustrated in following figure.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
• Altivar 212 drives up to
ATV212HD22N4S and
ATV212W075N4 can be removed
from their packaging and installed
without a handling device.
• A hoist must be used for higher
ratings.
• After removing the drive from its
packaging, inspect it for damage. If
any damage is found, notify the carrier
and your sales representative.
• Verify that the drive nameplate and
label conform to the packing slip and
corresponding purchase order.
45°
max.
Spreader
bar
Y
N
Lifting
force
Lifting
force
WARNING
RISK OF TOPPLING
Keep the drive on the pallet until ready to install.
Never place the drive in an upright position without proper support, such as a hoist, braces, or other
mounting supports.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTICE
RISK OF DERATED PERFORMANCE DUE TO CAPACITOR AGING
The product capacitor performances after a long time storage above 2 years can be degraded.
In that case, before using the product , apply the following procedure:
Use a variable AC supply connected between L1 and L2 (even for ATV212pppN4 references).
Increase AC supply voltage to have:
- 80% of rated voltage during 30 min
- 100% of rated voltage for another 30 min
Failure to follow these instructions can result in equipment damage.