Brochure
22-24
© 2019 Schneider Electric
All Rights Reserved
Commercial Pressure Switches
Type F—Pumptrol™ Water Pump Pressure
Switches
schneider-electric.us
Class 9013 / Refer to Catalog 9013CT9701
22
PRESSURE, VACUUM, AND FLOAT
SWITCHES
Type F Pressure Switch Selection and Features
Pressure Switch
•
Designed for the control of electrically driven water pumps. Diaphragm actuated.
•
Type FSG is the standard water pump switch, suitable for all types of pumps: jets,
submersible, reciprocating, etc.
•
Type FYG is designed to meet higher horsepower and pressure requirements.
•
Type FRG is reverse acting: contacts open on falling pressure.
Table 22.75: Pressure Codes
[7]
Standard Action Devices Reverse Action Devices
Settings
Code
Settings
Code
5–21 psi
J15
10–5 psi
J36
8–20 psi
J16
22–12 psi
J22
20–40 psi
J20
22–16 psi
J19
20–50 psi
J18
35–20 psi
J70
30–50 psi
J21
40–20 psi
J23
40–60 psi
J24
50–30 psi
J35
50–70 psi
J33
150–120 psi J64[8]
60–80 psi
J25
Specify other
pressure
J99[8]
Specify other
pressure
J99[8]
Table 22.76: Standard Action: Contacts Open On Rising Pressure
Cut-out
Range
(psig)
Approximate
Adjustable
Differential (psig)
Cut-in
Range
(psig)
Pressure Connection
2 Pole
NEMA 1
NEMA 3R[9]
Catalog No. Catalog No.
20–65 15–30 5–45
1/4" NPSF internal 9013FSG2 9013FSW2
1/4" NPT external 9013FSG9 9013FSW9
1/4" bayonet (barbed)
9013FSG10 9013FSW10
20–50 10–30 10–30 1/4" NPSF internal 9013FSG22 9013FSW22
20–60 10–30 10–45 1/4" NPT external 9013FSG29 9013FSW29
9–30 6–20 3–10 1/4" NPSF internal 9013FSG42 9013FSW42
9–30 6–20 3–10 1/4" NPT external 9013FSG49 9013FSW49
25–80 20–30 5–60
1/4" NPSF internal 9013FSG52 —
1/4" NPT external 9013FSG59 —
34–65 15–30 19–45
(FSG1 through 20 with Form M4 is only available in this range)
25–80 20–30 5–60
1/4" NPSF internal 9013FYG2 9013FYW2
1/4" NPT external 9013FYG9 9013FYW9
1/4" bayonet (barbed)
9013FYG10 9013FYW10
39–80 20–30 19–60
(FYG1 through 20 with Form M4 is only available in this range)
20–50 10–30 10–30 1/4" NPSF internal 9013FYG22 9013FYW22
20–60 10–30 10–45 1/4" NPT external 9013FYG29 9013FYW29
9–40 6–30 3–10 1/4" NPSF internal 9013FYG42 9013FYW42
9–40 6–30 3–10 1/4" NPT external 9013FYG49 9013FYW49
Table 22.77: Maximum Allowable Pressure
for All 9013 Switches
Type
Pressure
FHG, FSG, FYG, FSW, FYW, FRG
GHB, GHG, GSB, GSG
GMG, GSR, GSW
GHR, GHW
220 psig
300 psig
100 psig
250 psig
Table 22.78: Temperature Limitations
for All 9013 Switches
Operation (Media) Storage
–36 to +125 °C (–33 °F to +257 °F)
–36 to +125 °C (–33 to
+257 °F)
Table 22.79: Reverse Action: Contacts Open On Falling Pressure
Cut-in
Range
(psig)
Approximate
Adjustable Differential
(psig)
Cut-out Range
(psig)
Pressure
Connection
Catalog Number
1-Pole 2-Pole
23–65 15–30 8–45
1/4" NPSF internal 9013FRG12 9013FRG2
3/8" NPSF internal 9013FRG13 9013FRG3
1/4" NPT external 9013FRG19 9013FRG9
10–45 6–20 4–25
1/4" NPSF internal 9013FRG32 9013FRG22
3/8" NPSF internal 9013FRG33 9013FRG23
1/4" NPT external 9013FRG39 9013FRG29
6–14
5, Fixed
1–9
1/4" NPSF internal 9013FRG52 9013FRG42
3/8" NPSF internal 9013FRG53 9013FRG43
1/4" NPT external 9013FRG59 9013FRG49
40–100 20–30 20–80
1/4" NPSF internal 9013FRG72 9013FRG62
3/8" NPSF internal 9013FRG73 9013FRG63
65–150 30–45 35–120
1/4" NPSF internal 9013FRG92 9013FRG82
3/8" NPSF internal 9013FRG93 9013FRG83
1/4" NPT external 9013FRG99 9013FRG89
Ordering Information
•
Specify Class 9013 Type F.
•
Select the pressure code from Table 22.75, and add the code
designation to the end of the Type number. Ensure that the
pressure rating of the code falls within the limits of the device as
shown in Table 22.76 and Table 22.79.
•
To order special features from Table 22.80, add the appropriate
Form letter to the Class and Type. Arrange the Form letters in
alphabetical order when ordering more than one special feature.
See also:
•
Electrical Ratings For All 9013 Switches, page 22-
23
•
Dimensions, Type F, page 22-23
•
Renewal Parts for Class 9012–9038 Devices, page
22-34
[7] Existence of a code does not imply that the code is available for any or all devices.
[8] Minimum order quantity is 4 pieces.
[9] Must be mounted in vertical position to maintain enclosure rating.