Brochure

22-4
Pressure Sensors XMLG Pressure Transmitters and Switches
schneider-electric.us
Refer to Catalog 9014CT0201
22
PRESSURE, VACUUM, AND FLOAT
SWITCHES
XMLG Pressure Transmitters and Switches
XMLG●●●D
M12 Connector
XMLG●●●Q
Quick Connect
XMLG pressure transmitters and pressure switches are characterized by their ceramic
pressure-measuring cell. The deformation caused by the pressure is transmitted to the
resistors of a Wheatstone bridge silk-screened on the ceramic. The change in resistance
is then processed by the integrated electronics, providing either a digital or analog output
signal.
Table 22.1: Specifications
Enclosure Rating IP66, IP67 conforming to IEC/EN 60529, NEMA 4
Ambient Temperature (Operation) -15 to +85 °C (+5 to +185 °F)
Media Temperature -15 to +125 °C (+5 to +257 °F)
Precision (Linearity, Repeat Accuracy,
Hysteresis)
Transmitters: <0.3%; pressure/vacuum switches: <1%
Repeat Accuracy (PNP/NPN output) 0.1% of the measuring range
Current Consumption
Transmitters: < 20 mA
Pressure/vacuum switches: < 4 mA
Maximum Load Current
Transmitters: < 20mA
Pressure/vacuum switches: 150 mA switching capacity
Rated Voltage 12/24 V for transmitters and pressure/vacuum switches
Voltage Limits 24 V for transmitters and pressure/vacuum switches
Fluids Controlled
Hydraulic oils, air, fresh/sea water, corrosive fluids from -15 to +125
°C (+5 to +257 °F)
Materials in Contact with Fluid
Ceramic Al
2
O
3
, stainless steel type AISI 303, Viton
®
FPM, PPS
(leakage protection for P> 40 bar)
Output Response Time
< 2 ms
Table 22.2: Interpretation of the Catalog Number (example: XMLG100D23TQ)
XMLG 100 D 2 3
TQ
Units without Display, 22.8
mm diameter
Rated Pressure Range
Electrical
Connection
Output
Fluid Connection Bulk Pack
Code
psi
bar
M01 –14.5 to 0 –1 to 0 D: M12
1: DC Analog, 4–20 mA, shunt calibration
1: G 1/4 A
(BSP male)
001 0 to 14.5 0 to 1
Q: Integrated
quick connect
2: Analog, 4–20 mA
006 0 to 87.0 0 to 6
3: Solid state, NPN
3: 1/4" NPT male
010 0 to 145 0 to 10
4: Solid state, PNP
7: 7/16-20 UNF male
016 0 to 232.1 0 to 16
7: Analog, 0–10 V (bulk packs only)
025 0 to 362.5 0 to 25
11: DC Analog, 0–10 V shunt calibration
100 0 to 1450 0 to 100
160 0 to 2329.6 0 to 160
250 0 to 3625 0 to 250
400 0 to 5800 0 to 400
NOTE: Use this table only to interpret the catalog number. Some combinations are
not available.
Table 22.3: Selection
Rated Pressure Range
Fluid Connection Electrical Connection
Catalog Number[1][2]
Analog Output,
4–20 mA
Analog Output,
0–10 Vdc
-14.5 to 0 psi
-1 to 0 bar
1/4" NPT Male M12
XMLGM01D23 XMLGM01D73
0 to 14.5 psi
0 to 1 bar XMLG001D23 XMLG001D73
0 to 87 psi
0 to 6 bar XMLG006D23 XMLG006D73
0 to 145 psi
0 to 10 bar XMLG010D23 XMLG010D73
0 to 232 psi
0 to 16 bar XMLG016D23 XMLG016D73
0 to 362.5 psi
0 to 25 bar XMLG025D23 XMLG025D73
0 to 1450 psi
0 to 100 bar XMLG100D23 XMLG100D73
0 to 2320 psi
0 to 160 bar XMLG160D23 XMLG160D73
0 to 3625 psi
0 to 250 bar XMLG250D23 XMLG250D73
0 to 5800 psi
0 to 400 bar XMLG400D23 XMLG400D73
NOTE: For units with a solid-state output, the settings must be specified for each
order.
Table 22.4: Wiring Configurations (M12)
Output
Pin 1 Pin 3 Pin 4
Analog, 4–20 mA + Power supply Output
Analog, 0–10 Vdc + Power supply Output
Ground
Solid State, NPN
+ Power supply
Ground
Output
Solid State, PNP
+ Power supply
Ground
Output
UL E164865
CCN NKPZ
LR 44087
Class 3211-03
For wiring diagrams, refer to page 22-5.
[1] For devices with a switch output or 0–10 Vdc analog output, contact the Sensor Competency Center at 1-800-435-2121.
[2] For a bulk package (25 units), add TQ to the end of the catalog number. The minimum order quantity is 50 units (two bulk packs). When ordering, specify the individual number of units, NOT
the number of bulk packs. Minimum order quantity for factory ordered individual items (non-stock) is 50 pieces.
© 2016 Schneider Electric