Commercial Pressure Switches Type G—Pumptrol Pressure Switch
schneider-electric.us
Class 9013 / Refer to Catalog 9013CT9701
22
PRESSURE, VACUUM, AND FLOAT
SWITCHES
Table 22.62: Bulk Package Form Numbers for 9013F Pressure Switches
Description
Bulk Package Quantity
16 20 40 50 400 500
Product without
Forms M1, M3,
M4, M5, T, X1
9013FHG (without 1/4" four-way)
— C20 C50 — —
9013FHG4, 14, 24, 34, 44, 54 (with 1/4" four-way)
— C20 — C50 C400 —
9013FRG — C20 — C50 — —
9013FSG — C20 — C50 — —
9013FYG — C20 — C50 — —
Product with
Forms M1, M3,
M4, M5
9013FHG (without 1/4" four-way)
— C20 C40 — — —
9013FHG4, 14, 24, 34, 44, 54 (with 1/4" four-way)
— C20 C40 — — —
9013FRG — C20 C40 — — —
9013FSG — C20 C40 — — —
9013FYG — C20 C40 — — —
Product with
Forms T, X1
9013FHG (without 1/4" four-way)
C16 — C40 — — —
9013FHG4, 14, 24, 34, 44, 54 (with 1/4" four-way)
C16 — C40 — — —
9013FRG C16 — C40 — — —
9013FSG C16 — C40 — — —
9013FYG C16 — C40 — — —
9013FHG9 Special with Extended Flange
C16 — — — — C500
Type G Pressure Switch Selection and Features
™
Shown with
Form X
File
E12158
CCN
NKPZ
File
E12443
CCN
NOWT
Haz Loc
File
25490
File
26817
Haz.
Loc.
Table 22.63: Pressure Codes
Code
Pressure Setting (Close-Open), psi
J20 20–40
J21 30–50
J23
40–20 (reverse action)
J24 40–60
J25 60–80
J26 70–90
J28 70–100
J29 75–100
J30 80–100
J31 90–120
J50 135–175
J51
100–80 (reverse action)
J53 100–125
J54 110–125
J56 110–150
J57 120–150
J58 125–150
J60 125–175
J61 130–175
J62 140–175
J63 145–175
J64
150–120 (reverse action)
J65 215–250
J99
Specify the required setting
Table 22.64: Special Features and Modifications
Description Form Letter
3-Way Lever (On-Auto-Off) E
One Normally Open / One Normally Closed
Contact
H
Pulsation Plug P
Reverse Action R
Slip-On Connectors (Load Side Terminals Only) U
Slip-On Connectors (Line and Load Terminals) U2
Two-Way Pressure Release Valve X
¼" Male Pipe Thread on Pressure Connection Z
½"-14 NPT External
¼"-18 NPT Internal
Z16
Class 9013 Type G Pumptrol pressure switches are designed to control electrically
driven water pumps and air compressors. These devices cover higher electrical ratings
for directly controlling motors in pump and compressor applications.
•
Contacts open on pressure rise.
•
Diaphragm actuated.
•
For electrical ratings, see .
For repair parts kits, see page 22-30.
Table 22.65: Selection Tables
Cut-out
Range
(psig)
Approximate
Adjustable
Differential
(psig)
Cut-in
Range
(psig)
Enclosure Poles
NPSF Internal
Pressure
Connection
Type
10–35 4–8 5.5–30.5
NEMA 1 (General Purpose)
2 1/4 GMG2
20–80 15–30 5–60
NEMA 3R [13] (Rainproof)
2 1/4 GSB2
20–80 15–30 5–60
NEMA 1 (General Purpose)
2
1/8 GSG1
1/4 GSG2
3/8 GSG3
20–80 20–40 5–50
NEMA 7 & 9
(Hazardous Locations)
2
1/8 GSR1
1/4 GSR2
3/8 GSR3
NEMA 4 (Watertight)
1/8 GSW1
1/4 GSW2
3/8 GSW3
65–200 20–40 40–170
NEMA 3R [13] (Rainproof)
2 1/4 GHB2
65–200 20–40 40–170
NEMA 1 (General Purpose)
2
1/8 GHG1
1/4 GHG2
3/8 GHG3
65–200 30–50 35–150
NEMA 7 & 9
(Hazardous Locations)
2
1/8 GHR1
1/4 GHR2
3/8 GHR3
NEMA 4 (Watertight)
1/8 GHW1
1/4 GHW2
3/8 GHW3
80–250 25–45 32–215
NEMA 3R [13] (Rainproof)
2 1/4 GHB5
80–250 24–45 32–215
NEMA 1 (General Purpose)
2
1/8 GHG4
1/4 GHG5
3/8 GHG6
80–250 40–60 30–190
NEMA 7 & 9
(Hazardous Locations)
2
1/8 GHR4
1/4 GHR5
3/8 GHR6
NEMA 4 (Watertight)
1/8 GHW4
1/4 GHW5
3/8 GHW6
NOTE: Some product configurations are not available. Contact your Schneider
Electric representative for details.
Ordering Information
•
Specify Class 9013 Type G.
•
Select the pressure code from Table 22.63, and add the code to the end of the Type
number. Ensure that the pressure rating of the code falls within the limits of the device.
See Table 22.65.
•
To order special features, add the appropriate Form letter to the Class and Type.
Arrange Form letters in alphabetical order when ordering more than one special
feature.
[13] Must be mounted in vertical position to maintain enclosure rating.
© 2016 Schneider Electric
All Rights Reserved