Brochure

22-14
Pressure Switches Machine Tool, Type G
schneider-electric.us
Class 9012 / Refer to Catalog 9012CT9701
22
PRESSURE, VACUUM, AND FLOAT
SWITCHES
Control Circuit Rated Type G Pressure Switches
9012GAW5
NEMA 4, 4X, 13
Class 9012 single stage pressure switches are control circuit rated devices used in pneumatic or hydraulic systems on a wide variety of machine
and process applications to protect the equipment and control or monitor the system pressure.
Type G machine tool switches are available with NEMA Type 4, 4X, and 13 (IEC IP66) enclosure ratings.
The NEMA 7 and 9 devices are UL listed for use in the following hazardous locations: Class I, Divisions 1 and 2, Groups C and D; and Class II,
Divisions 1 and 2, Groups E, F, and G.
Enclosure materials are cast aluminum.
To ensure repeatability and minimize setting drift, pressure settings should fall within the middle 80 percent of the pressure range.
Table 22.30: Fixed Differential[5]
NEMA 4, 4X, 13 Enclosure
UL Listed and CSA Certified As Industrial Control Equipment
Range on
Decreasing
Pressure
psig
[6]Approximate
Differential at
Mid-Range
psig
Maximum
Allowable
Pressure
psig
Single Pole
Double Throw
Double Pole
Double Throw
Type Type
Diaphragm Actuated—Nitrile (Buna-N) Diaphragm, Zinc Plated Steel Housing
.2–10 0.6 ±0.1 100 GDW1 GDW21
1–40 1.6 ±0.4 100 GDW2 GDW22
1.5–75 3.0 ±0.5 240 GDW4 GDW24
3–150 6.0 ±0.8 475 GDW5 GDW25
5–250 10.0 ±1.5 750 GDW6 GDW26
13–425 16 ±3.5 850 GEW1 GEW21
20–675 27 ±5 2000 GEW2 GEW22
Piston Actuated—#440 Stainless Steel Piston. #303 Stainless Steel Housing,
Viton
®
Fluorocarbon Diaphragm and O-ring, Teflon
®
Retaining Ring
20–1000 59 ±9 10000 GFW1 GFW21
90–2900 170 ±15 15000 GFW2 GFW22
170–5600 289 ±55 20000 GFW3 GFW23
270–9000 495 ±70 25000 GFW4 GFW24
Table 22.31: Adjustable Differential [5]
NEMA 4, 4X, 13 EnclosureUL Listed and CSA Certified As
Industrial Control Equipment
Range on
Decreasing
Pressure
psig
[6]Adjustable
Differential
Approximate
at Mid-Range
Maximum
Allowable
Pressure
psig
Single Pole
Double Throw
Double Pole
Double Throw
Type Type
Diaphragm Actuated—Nitrile (Buna-N) Diaphragm, Zinc Plated Steel Housing
.2–10 0.6–2 100 GAW1 GAW21
1–40 1.6–8 100 GAW2 GAW22
1.5–75 3.5–15 240 GAW4 GAW24
3–150 6.0–30 475 GAW5 GAW25
5–250 10.0–49 750 GAW6 GAW26
13–425 16–90 850 GBW1 GBW21
20–675 27–130 2000 GBW2 GBW22
Piston Actuated—#440 Stainless Steel Piston. #303 Stainless Steel Housing,
Viton Fluorocarbon Diaphragm and O-ring, Teflon
®
Retaining Ring
20–1000 59–200 10000 GCW1 GCW21
90–2900 170–560 15000 GCW2 GCW22
170–5600 289–1260 20000 GCW3 GCW23
270–9000 495–1900 25000 GCW4 GCW24
Table 22.32: Fixed Differential
NEMA 7 & 9 Enclosure
Class I & II, Division 1 & 2, Groups C, D, E, F, G
Range on
Decreasing
Pressure
psig
[6]Approximate
Differential at
Mid-Range
psig
Maximum
Allowable
Pressure
psig
Single Pole
Double Throw
Double Pole
Double Throw
Type Type
Diaphragm Actuated—Nitrile (Buna-N) Diaphragm, Zinc Plated Steel Housing
0.2–10 1.0 ±0.1 100 GDR1
1–40 2.4 ±0.8 100 GDR2 GDR22
1.5–75 4.5 ±1 240 GDR4 GDR24
3–150 9 ±1.5 475 GDR5 GDR25
5–250 15 ±3 750 GDR6 GDR26
13–425 25 ±7 850 GER1 GER21
Piston Actuated—#440 Stainless Steel Piston. #303 Stainless Steel Housing,
Viton Fluorocarbon Diaphragm and O-ring, Teflon
®
Retaining Ring
20–1000 89 ±18 10000 GFR1 GFR21
90–2900 255 ±30 15000 GFR2 GFR22
170–5600 578 ±110 20000 GFR3
Acceptable Wire Sizes: 12–22 AWG
Recommended Terminal Clamp Torque: 7 lb-in
Electrical Rating: see page 22-16
Temperature Rating: see page 22-16
Modifications: see page 22-18
Accessories: see page 22-18
Renewal Parts Kits: see page 22-30
Dimensions: see page 22-17
Table 22.33: Adjustable Differential
NEMA 7 & 9 Enclosure
Class I & II, Division 1 & 2, Groups C, D, E, F, G
Range on
Decreasing
Pressure
psig
[6]Adjustable
Differential
Approximate
at Mid-Range
Maximum
Allowable
Pressure
psig
Single Pole
Double Throw
Double Pole
Double Throw
Type Type
Diaphragm Actuated—Nitrile (Buna-N) Diaphragm, Zinc Plated Steel Housing
0.2–10 1.0–2 100 GAR1 GAR21
1–40 2.4–8 100 GAR2 GAR22
1.5–75 4.5–15 240 GAR4 GAR24
3–150 9–35 475 GAR5 GAR25
5–250 15–49 750 GAR6 GAR26
13–425 25–90 850 GBR1 GBR21
20–675 41–130 2000 GBR2 GBR22
Piston Actuated—#440 Stainless Steel Piston. #303 Stainless Steel Housing,
Viton Fluorocarbon Diaphragm and O-ring, Teflon
®
Retaining Ring
20–1000 89–200 10000 GCR1 GCR21
90–2900 255–560 15000 GCR2
170–5600 578–1260 20000 GCR3 GCR23
270–9000 788–1900 25000 GCR4
Complies with IEC 60957.5.1,
5C8.3.4 when protected with a
Bussmann CCKTK-R-10 fuse.
File: E12443 Haz.
Loc.
CCN NOWT G•R
File:
LR25490
Class 3211-03
G•W, G•O, G•G
File: E12158 CCN NKPZ
G•O, G•G, G•W
File:
LR26817
Class 3218-02 G*R
File: E12158 CCN NTHT
Marine Use, G•W
[5] For metric threads, add M after the W on all types (offered at an additional cost).
To order a Pg13.5 electrical conduit entry and a 1/4”-19 BSP pressure connection, add M12 to the end of the catalog number, as well as adding “M” after “W” for metric threads. For example:
9012GAW1 = 1/2” NPT electrical conduit entry
9012GAWM1 = 20 x 1.5 mm electrical conduit entry
9012GAWM1M12 = Pg13.5 electrical conduit entry and 1/4-19 BSP pressure connection.
[6] The differential adds to the range setting and determines the operating point on rising pressure.
© 2016 Schneider Electric
All Rights Reserved
9/24/2016