Use and Care Guide

Optional features available for the 9013 standard action product line
Many optional features are available to increase the functionality and performance of your Schneider Electric pressure
switches. See the table below to identify the feature which you may need for your application.
* Nylon pulsation plug can be eld installed on types having 1/4" NPSF internal connector. Part number 1530S6G1 is one bag of 50 plugs
** Change uid connection code in the product part
– 1/4" barbed bayonet (example: 9013FSG10)
– 90° elbow 1/4" barbed bayonet (example: 9013FSG20)
*** Use chart to interpret catalog number only
2 and 9 are the uid connections
9013FSG standard
action, fully-adjustable
differential
9013FTG standard
action, non-adjustable
differential
9013FYG standard
action, fully-adjustable
with higher HP rating
M1 Maintained manual on/off lever (auto-off) Yes No Yes
M4 Low pressure cut-off (auto-start-off) Yes No Yes
B7 One rubber grommet, export only Yes Yes Yes
B8 Two rubber grommets, export only Yes Yes Yes
T 1/2" conduit bushing per the National Electric Code
®
(NEC
®
) Yes Yes Yes
Q1 Plastic ange with integral molded pressure Yes No Yes
P* Optional pulsation plug Yes Yes Yes
10** Bayonet (barbed) pressure connector Yes Yes Yes
20** 90° elbow with 1/4" bayonet Yes Yes Yes
Z22 Black cover Yes Yes Yes
U Slip-on connector, load Yes Yes Yes
U2 Slip-on connector, line and load Yes Yes Yes
Explanation of a part number (example: 9013FSG2J21P)***
9013 + FS + G + 2 + J21 + P
Class Type Enclosure Fluid Pressure Forms
Connection Codes
Type
FS = Standard-adjustable differential
FY = Higher HP with adjustable differential
FT = Non-adjustable differential
Enclosure
G = NEMA 1 W = NEMA 3R
Fluid Connection
1 = 1/8" NPSF internal threads
2 = 1/4" NPSF internal
9 = 1/4" NPT external
10 = 1/4" bayonet, barbed
20 = 90° elbow, 1/4" bayonet
4 = Narrow differential
42
= 9-30 PSIG cut-out, 3-10 cut-in
49
= 9-30 PSIG cut-out, 3-10 cut-in
52 = 25-80 PSIG cut-out,10-60 cut-in
59 = 25-80 PSIG cut-out,10-60 cut-in
Others available
Pressure Codes
J20 = 20-40 PSI
J21 = 30-50 PSI
J24 = 40-60 PSI
J25 = 60-80 PSI
J33 = 50-70 PSI
J34 = 55-85 PSI
J99 = Specify range
Others available
Forms
M1 = Maintained manual cut-off lever
M4 = Low pressure cut-off
B7 = One rubber grommet
B8 = Two rubber grommets
Q8 = Plastic ange
P = Pulsation plug
T = 1/2" conduit bushing on left
U = Slip-on connector, load
U2 = Slip-on connector, line and load
Z22 = Black cover