Motor Control Solutions Combination Starter Construction Types 
12 © 2013–2017 Schneider Electric All Rights Reserved 8536DB0901R09/16
On the branch circuit, the following are permitted as the disconnecting means when 
installed between the final motor branch circuit short circuit protection and the 
motor: 
• Any UL 508 switch that is suitable as a motor disconnect (according to NEC 
Section 430.81), which is used to start and stop a motor
• A manual motor controller that is suitable as a motor disconnect (according to 
NEC Section 430.109)
Motor Starter Line Diagrams
Figure 4 – Power Supply Circuit 
or 
TeSys GS
UL 98 
or 
PowerPact 
UL 489 
PowerPact 
UL 489 
M 
TeSys U 
UL 508 
Type E 
TeSys 
GV2P + LC1D 
GV3P + LC1D 
UL 508 Type F 
TeSys 
GV2ME + LC1D 
UL 508 
Group Installation 
M M M M M
TeSys GV2P or GV3P 
UL 508 Type E 
+ LC1D if needed
+ Altivar drives 
Other 
Loads 
LC1D 
if needed 