Motor Control Solutions Group Motor Installations
46 © 2013–2017 Schneider Electric All Rights Reserved 8536DB0901R09/16
TeSys™ GV3P + TeSys D Contactors
Group Motor Installations
UL 508 Group Motor Installations
TeSys™ GV2ME + TeSys D Contactors
Table 69 – TeSys GV3P Type F Combination Motor Starter (UL File E164871)
In combination with line spacer GV3G66 and short circuit signaling
contact GVAM11 for stand-alone starters
Manual
Self-
Protected
Starter
Overload Trip
Range (A)
Maximum Horsepower Ratings
Type of Contactor
Required
SCCR (kA)
Single-
Phase
Three-Phase
480Y/
277V
600Y/
347V
120 V 240 V 208 V 240 V 480 V 600 V
GV3P13 9–13 0.5 1.5 3 3 7.5 10
LC1D18, D25, D32,
D40A, D50A, or D65A
65 25
GV3P18 12–18 0.75 2 5 5 10 15
LC1D18, D25, D32,
D40A, D50A, or D65A
65 25
GV3P25 17–25 1.5 3 5 7.5 15 20
LC1D25, D32, D40A,
D50A, or D65A
65 25
GV3P32 23–32 2 5 7.5 10 20 25
LC1D32, D40A,
D50A, or D65A
65 25
GV3P40 30–40 3 10 25 30
LC1D40A, 50A, or
65A
65 25
GV3P50 37–50 7.5 10 15 30 40 LC1D50A or 65A 65 25
GV3P65 48–65 5 10 15 20 40 50 LC1D65A or 80 65 25
NOTE: Type F ratings only valid at 600Y/347 V and 480Y/277 V voltages and lower.
TeSys GV3P with TeSys D
GV3G66 + GV3P40 +
GVAM11 + LC1D40A
GV2ME07 with LC1D09
Table 70 – TeSys GV2ME and TeSys D Contactors for Group Motor
Installations (UL File E164864)
In association with LC1D contactors, suitable for Group Installation
when protected by fuses or a circuit breaker (including multi starter
with GV1G09 or GV2G05 blocks plus GV2G busbars)
Manual
Motor
Starter
Overload
Trip
Range
(A)
Maximum Horsepower Ratings SCCR (kA)
1
Single-
Phase
Three-Phase Type of
Contactor
Required
480 V
600Y /
347 V
480 V
with
GV1L3
Limiter
120 V 240 V 208 V 240 V 480 V 600 V
GV2ME01 0.10–0.16 LC1D09 or D12 65 42 65
GV2ME02 0.16–0.25 LC1D09 or D12 65 42 65
GV2ME03 0.25–0.40 LC1D09 or D12 65 42 65
GV2ME04 0.40–0.63 LC1D09 or D12 65 42 65
GV2ME05 0.63–1 0.5 LC1D09 or D12 65 42 65
GV2ME06 1–1.6 1/10 0.75 0.75 LC1D09 or D12 65 42 65
GV2ME07 1.6–2.5 1/6 0.5 0.5 1 1.5 LC1D09 or D12 65 42 65
GV2ME08 2.5–4 1/8 1/3 0.75 0.75 2 3 LC1D09 or D12 65 42 65
GV2ME10 4–6.3 0.25 0.5 1 1.5 3 5 LC1D09 or D12 65 42 65
GV2ME14 6–10 0.5 1.5 2 3 5 7.5 LC1D09 or D12 65 42 65
GV2ME16 9–14 0.75 2 3 3 10 10 LC1D12 or D18 22 10 65
GV2ME20 13–18 1 3 5 5 10 15 LC1D12 or D18 22 10 65
GV2ME21 17–23 1.5 3 5 7.5 15 20 LC1D25 or D32 10 10 65
GV2ME22 20–25 2 7.5 7.5 15 20 LC1D25 or D32 10 10 65
GV2ME32 24–32 2 5 7.5 10 20 25 LC1D25 or D32 5 5 65
1