Specification
Motor Control Solutions Group Motor Installations
46 © 2013–2017 Schneider Electric All Rights Reserved 8536DB0901R09/16
TeSys™ GV3P + TeSys D Contactors
Group Motor Installations
UL 508 Group Motor Installations
TeSys™ GV2ME + TeSys D Contactors
Table 69 – TeSys GV3P Type F Combination Motor Starter (UL File E164871)
In combination with line spacer GV3G66 and short circuit signaling
contact GVAM11 for stand-alone starters
Manual
Self-
Protected
Starter
Overload Trip
Range (A)
Maximum Horsepower Ratings
Type of Contactor
Required
SCCR (kA)
Single-
Phase
Three-Phase
480Y/
277V
600Y/
347V
120 V 240 V 208 V 240 V 480 V 600 V
GV3P13 9–13 0.5 1.5 3 3 7.5 10
LC1D18, D25, D32,
D40A, D50A, or D65A
65 25
GV3P18 12–18 0.75 2 5 5 10 15
LC1D18, D25, D32,
D40A, D50A, or D65A
65 25
GV3P25 17–25 1.5 3 5 7.5 15 20
LC1D25, D32, D40A,
D50A, or D65A
65 25
GV3P32 23–32 2 5 7.5 10 20 25
LC1D32, D40A,
D50A, or D65A
65 25
GV3P40 30–40 3 — 10 — 25 30
LC1D40A, 50A, or
65A
65 25
GV3P50 37–50 — 7.5 10 15 30 40 LC1D50A or 65A 65 25
GV3P65 48–65 5 10 15 20 40 50 LC1D65A or 80 65 25
NOTE: Type F ratings only valid at 600Y/347 V and 480Y/277 V voltages and lower.
TeSys GV3P with TeSys D
GV3G66 + GV3P40 +
GVAM11 + LC1D40A
GV2ME07 with LC1D09
Table 70 – TeSys GV2ME and TeSys D Contactors for Group Motor
Installations (UL File E164864)
In association with LC1D contactors, suitable for Group Installation
when protected by fuses or a circuit breaker (including multi starter
with GV1G09 or GV2G05 blocks plus GV2G busbars)
Manual
Motor
Starter
Overload
Trip
Range
(A)
Maximum Horsepower Ratings SCCR (kA)
1
Single-
Phase
Three-Phase Type of
Contactor
Required
480 V
600Y /
347 V
480 V
with
GV1L3
Limiter
120 V 240 V 208 V 240 V 480 V 600 V
GV2ME01 0.10–0.16 — — — — — — LC1D09 or D12 65 42 65
GV2ME02 0.16–0.25 — — — — — — LC1D09 or D12 65 42 65
GV2ME03 0.25–0.40 — — — — — — LC1D09 or D12 65 42 65
GV2ME04 0.40–0.63 — — — — — — LC1D09 or D12 65 42 65
GV2ME05 0.63–1 — — — — — 0.5 LC1D09 or D12 65 42 65
GV2ME06 1–1.6 — 1/10 — — 0.75 0.75 LC1D09 or D12 65 42 65
GV2ME07 1.6–2.5 — 1/6 0.5 0.5 1 1.5 LC1D09 or D12 65 42 65
GV2ME08 2.5–4 1/8 1/3 0.75 0.75 2 3 LC1D09 or D12 65 42 65
GV2ME10 4–6.3 0.25 0.5 1 1.5 3 5 LC1D09 or D12 65 42 65
GV2ME14 6–10 0.5 1.5 2 3 5 7.5 LC1D09 or D12 65 42 65
GV2ME16 9–14 0.75 2 3 3 10 10 LC1D12 or D18 22 10 65
GV2ME20 13–18 1 3 5 5 10 15 LC1D12 or D18 22 10 65
GV2ME21 17–23 1.5 3 5 7.5 15 20 LC1D25 or D32 10 10 65
GV2ME22 20–25 2 — 7.5 7.5 15 20 LC1D25 or D32 10 10 65
GV2ME32 24–32 2 5 7.5 10 20 25 LC1D25 or D32 5 5 65
1
Ratings apply to circuit with voltages no greater than those listed.