Combination Starter Solutions Motor Control Solutions
45© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
UL 508 Type F
Construction Type F is similar to Type E, but uses two devices. The disconnecting
means, motor branch circuit protection, and motor overload relay functions are all
combined into one device, a UL 508 manual self-protected combination controller
while the motor controller is kept separate in the form of a UL 508 contactor.
Schneider Electric offers the following solution for this construction type:
TeSys™ GV2P + TeSys D Contactors
Manual Self-Protected Combination Starter Meeting UL 508 Type F
UL File E164871
Table 67 – Self-Protected Combination Motor Controller using a UL 508 Manual
Self-Protected Combination Controller and a UL 508 Contactor
UL 508 Manual Self-Protected Combination Controller UL 508 Contactor
-TeSys GV2P
-TeSys GV3P
-TeSys D
Table 68 – TeSys GV2P Type F Combination Motor Starter (UL File E164871)
In combination with line spacer GV2GH7 or GV1G09 for stand-alone
starters or line spacer GV1G09 with GV2G busbars for multiple starters
Manual
Self-
Protected
Starter
Overload
Trip
Range (A)
Maximum Horsepower Ratings
Type of
Contactor
Required
SCCR (kA)
Single-Phase Three-Phase
480Y /
277 V
600Y /
347 V
120 V 240 V 208 V 240 V 480 V 600 V
GV2P01 0.10–0.16 — — — — — —
LC1D09 or D12 100 —
LC1D09 100 50
GV2P02 0.16–0.25 — — — — — —
LC1D09 or D12 100 —
LC1D09 100 50
GV2P03 0.25–0.40 — — — — — —
LC1D09 or D12 100 —
LC1D09 100 50
GV2P04 0.40–0.63 — — — — — —
LC1D09 or D12 100 —
LC1D09 100 50
GV2P05 0.63– 1 — — — — — 0.5
LC1D09 or D12 100 —
LC1D09 100 50
GV2P06 1–1.6 — 1/10 — — 0.75 0.75
LC1D09 or D12 100 —
LC1D09 100 50
GV2P07 1.6–2.5 — 1/6 0.5 0.5 1 1.5
LC1D09 or D12 100 —
LC1D09 100 50
GV2P08 2.5– 4 1/8 1/3 0.75 0.75 2 3
LC1D09 or D12 100 —
LC1D09 100 50
GV2P10 4–6.3 0.25 0.5 1 1.5 3 5
LC1D09 or D12 100 —
LC1D09 100 50
GV2P14 6–10 0.5 1.5 2 3 5 7.5
LC1D09 or D12 100 —
LC1D09 100 50
GV2P16 9–14 0.75 2 3 3 10 10
LC1D12 or D18 42 —
LC1D18 50 50
GV2P20 13–18 1 3 5 5 10 15
LC1D12 or D18 42 —
LC1D18 50 50
GV2P21 17–23 1.5 3 5 7.5 15 20
LC1D25 or D32 42 —
LC1D25 50 50
GV2P22 20–25 2 — 7.5 7.5 15 20
LC1D25 or D32 42 —
LC1D25 50 50
NOTE: Type F ratings only valid at 600Y/347V and 480Y/277V voltages and lower.
TeSys GV2P with TeSys D
GV2GH7 + GV2P10 +
GV2AF3+ LC1D09