Specification
Motor Control Solutions Combination Starter Components
42 © 2013–2017 Schneider Electric All Rights Reserved 8536DB0901R09/16
UL 508 Manual Self-Protected Combination Motor Controller (Type E)
TeSys™ GV2P
TeSys™ GV3P
GV2P10 with GV2GH7
Table 57 – TeSys GV2P Manual Self-Protected Combination Motor Starter
(UL File E164871)
In combination with line spacer GV2GH7 or GV1G09 for stand-alone
starters or line spacer GV1G09 with GV2G busbars for multiple
starters.
Manual
Self-
Protected
Starter
Overload
Trip Range
(A)
Maximum Horsepower Ratings SCCR (kA)
Single-Phase Three-Phase
480Y/277 V 600Y/347 V
120 V 240 V 208 V 240 V 480 V 600 V
GV2P01 0.10–0.16 — — ———— 100 50
GV2P02 0.16–0.25 — — ———— 100 50
GV2P03 0.25–0.40 — — ———— 100 50
GV2P04 0.40–0.63 — — ———— 100 50
GV2P05 0.63–1 — — — — — 0.5 100 50
GV2P06 1–1.6 — 1/10 — — 0.75 0.75 100 50
GV2P07 1.6–2.5 — 1/6 0.5 0.5 1 1.5 100 50
GV2P08 2.5–4 1/8 1/3 0.75 0.75 2 3 100 50
GV2P10 4–6.3 0.25 0.5 1 1.5 3 5 100 50
GV2P14 6–10 0.5 1.5 2 3 5 7.5 100 22
GV2P16 9–14 0.75 2 3 3 10 10 10 —
GV2P20 13–18 1 3 5 5 10 15 10 —
GV2P21 17–23 1.5 3 5 7.5 15 20 10 —
GV2P22 20–25 2 — 7.5 7.5 15 20 10 —
NOTE: Type E ratings are only valid at 600Y/347 V and 480Y/277 V voltages and lower.
GV3P40 with GV3G66 and
GVAM11
Table 58 – TeSys GV3P Manual Self-Protected Combination Motor Starter
(UL File E164871)
In combination with line spacer GV3G66 and short circuit signaling
contact GVAM11 for stand-alone starters
Manual Self-
Protected
Starter
Overload
Trip Range
(A)
Maximum Horsepower Ratings SCCR (kA)
1Ø 3Ø
480Y /
277 V
600Y /
347 V
120V 240 V 208 V 240 V 480 V 600 V
GV3P13 9–13 0.5 1.5 3 3 7.5 10 100 25
GV3P18 12–18 0.75 2 3 5 7.5 10 100 25
GV3P25 17–25 1.5 3 5 7.5 15 20 100 25
GV3P32 23–32 2 3 7.5 7.5 20 25 100 25
GV3P40 30–40 3 5 10 10 25 30 65 25
GV3P50 37–50 3 7.5 10 10 30 40 65 25
GV3P65 48–65 3 10 15 15 40 50 65 25
NOTE: Type E ratings are only valid at 600Y/347 V and 480Y/277 V voltages and lower.