Specification
Combination Starter Components Motor Control Solutions
39© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
Type S Starters
Table 51 – TeSys N Starter Maximum Component SCCR
1
Catalog
Number
Circuit Breakers @ 480 V
2
Circuit Breakers @ 600 V
2
Fuses @ 600 V
Max. Breaker
Size (A)
Max. SCCR
(kA)
Max. Breaker
Size (A)
Max. SCCR
(kA)
Max. Fuse
Size (A)
Max. SCCR
(kA)
T36AN13 60 85 60 50 60
3
100
T36BN13 60 85 60 50 80
3
100
T36CN13 60 85 60 50 80
3
100
T36DN13 110 100 110 50 125
3
100
T36EN13 200 65 * 10 200
3
100
T36FN13 250 65 * 10 200
3
100
T36GN13 * 18 * 18 600
3
100
T36HN13 * 30 * 30 1000 30
T36JN13 * 42 * 42 1200 42
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
3
When protected by any Class J or CC time-delay fuse.
* Per NEC Table 430.52
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum component SCCR is 100 kA
and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the circuit breaker becomes the weakest link.
Type S Starter with Motor Logic
8536SBO2
Table 52 – Type S Starters with Motor Logic or TeSys T Overload Relays
Catalog
Number
Standard Motor Ratings
@ 50/60 Hz (HP)
Continuous
Current
Rating (A)
NEMA
Size
Max. Component
SCCR (kA)
1
1
Ratings apply to circuits with voltages no greater than those listed.
Three-Phase Circuit
Breakers
@ 480 V
2
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in
Table 53.
Fuses @
600 V
208 V 240 V 480 V 600 V
8536SAO12 1.5 1.5 2 2 9 00 100 100
3
3
When protected by any Class RK5, RK1, T, or J fuse, meeting the size limits in Table 53.
8536SBO2 3 3 5 5 18 0 100 100
3
8536SCO2 7.5 7.5 10 10 27 1 100 100
3
8536SDO1 10 15 25 25 45 2 100 100
3
8536SEO1 25 30 50 50 90 3 100 100
3
8536SFO1 40 50 100 100 135 4 100 100
4
4
When protected by any Class T or J fuse, meeting the size limits in Table 53.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
8536SGO1 75 100 200 200 270 5 100 100
4
8536SHO2 150 200 400 400 540 6 65 100
4
8536SJO2 — 300 600 600 810 7 30 30