Specification

Combination Starter Components Motor Control Solutions
37© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
TeSys™ LR9F Electronic Overload Relays
TeSys™ T Motor Management System
TeSys F Overload Relay
LR9F5
Table 47 – TeSys LR9F Electronic Overload Relays
1
1
When mounting overload relays LR9F5*57 to LR9F5*71 directly beneath the contactor, supporting the relays with a
mounting plate is recommended. With overload relays LR9F7*75 to LR9F7*81, use of a support mounting plate is
mandatory.
Current
Setting
Range
(A)
For Direct
Mounting
to LC1…
Class 10 Class 20
Max. Component SCCR (kA)
2
2
Ratings apply to circuits with voltages no greater than those listed.
Circuit Breakers
@ 480 V
3
3
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
Circuit Breakers
@ 600 V
3
Fuses
@ 600 V
4
4
When protected by any Class J time-delay fuse.
Max.
Breaker
Size (A)
Max.
SCCR
(kA)
Max.
Breaker
Size (A)
Max.
SCCR
(kA)
Max.
Fuse
Size (A)
Max.
SCCR
(kA)
30–50
F115–F185
LR9F5357 LR9F5557 90 100
48–80 LR9F5363 LR9F5563 150 100
60–100 LR9F5367 LR9F5567 175 100 175 50 225 100
90–150 LR9F5369 LR9F5569 250 100 250 50 400 100
132–220 F185–F265
5
5
Interconnection kit LA7F407 is required to mount an LR9F5*71 to an LC1F185.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 65 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
LR9F5371 LR9F5571 250 65
200–330
F265–F500
LR9F7375
LR9F7575
300–500 LR9F7379 LR9F7579
380–630 F400–F630 LR9F7381 LR9F7581
Table 48 – TeSys T Motor Management System
Current Range (A)
Catalog Number
1
Max. Component SCCR (kA)
2
Control Voltage
Circuit Breakers
(kA)
3
Fuses (kA)
24 Vdc 100-240 Vac
0.4–8 LTMR08*BD LTMR08*FM 100 100
1.35–27 LTMR27*BD LTMR27*FM 100 100
5–100 LTMR100*BD LTMR100*FM 100 100
1
The "*" represents the type of fieldbus. Replace the "*" with a M for Modbus, a P for Profibus DP, an E for Ethernet
TCP/IP, a C for CANopen, and a D for DeviceNet.
2
Ratings apply to circuits no greater than 600 V.
3
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
TeSys T Motor Management
System
LTMR08MFM