Specification
Combination Starter Components Motor Control Solutions
33© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
TeSys™ NEMA Lighting Contactors
TeSys NEMA Lighting Contactor
LC1D25MEQ4096
Table 42 – TeSys NEMA Lighting Contactors
Contact
Ampere
Ratings
No. of
Poles
Catalog Number Max. Component SCCR (kA)
1
1
Ratings apply to circuits with voltages no greater than those listed.
Electrically Held
Circuit Breakers
@ 480 V
2
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in
Table 43.
Circuit
Breakers @
600 V
2
Fuses @
600 V
3
3
When protected by any Class J or CC time-delay fuse meeting the size limits in Table 43.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
30 3 LC1D25MEQ4096 85 50 100
60 3 LC1D40AMEQ4096 100 50 100
100 3 LC1D80MEQ4096 100 50 100
150 3 LC1D150MEQ4096 100 50 100
Table 43 – TeSys NEMA Lighting Contactor Maximum Component SCCR
1
1
Ratings apply to circuits with voltages no greater than those listed.
Catalog Number
Circuit Breakers @ 480 V
2
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
Circuit Breakers @ 600 V
2
Fuses @ 600 V
3
3
When protected by any Class J or CC time-delay fuse.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
Max. Breaker
Size (A)
Max. SCCR
(kA)
Max.
Breaker
Size (A)
Max. SCCR
(kA)
Max.
Fuse Size
(A)
Max. SCCR
(kA)
LC1D25MEQ4096 60 85 60 50 60 100
LC1D40AMEQ4096 110 100 110 50 90 100
LC1D80MEQ4096 150 100 150 50 175 100
LC1D150MEQ4096 250 100 250 50 300 100