Specification

Combination Starter Components Motor Control Solutions
31© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
Type S Lighting Contactors
Type S Lighting
Contactor
8903SPO3V02
Table 38 – Type S Lighting Contactors
Contact
Ampere
Ratings
No. of
Poles
Catalog Number, Open Type
Max. Component
SCCR (kA)
1
1
Ratings apply to circuits with voltages no greater than those listed.
Electrically Held Mechanically Held
Circuit Breakers @
480 V
2
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in
Table 39.
Fuses @ 600 V
3
3
When protected by any Class RK5, RK1, T or J fuse, meeting the size limits in Table 39.
30
2 8903SMO1 8903SMO10
100 100
3
3 8903SMO2 8903SMO11
4 8903SMO3 8903SMO12
5 8903SMO4 8903SMO13
60
2 8903SPO1 8903SPO10
100 100
3
3 8903SPO2 8903SPO11
4 8903SPO3 8903SPO12
5 8903SPO4 8903SPO13
100
2 8903SQO1 8903SQO10
100 100
3
3 8903SQO2 8903SQO11
4 8903SQO3 8903SQO12
5 8903SQO4 8903SQO13
200
2 8903SVO1 8903SVO10
100 100
4
4
When protected by any Class T or J fuse, meeting the size limits in Table 39.
This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum
component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the circuit
breaker becomes the weakest link.
3 8903SVO2 8903SVO11
4 8903SVO3 8903SVO12
5 8903SVO4 8903SVO13
300
2 8903SXO1 8903SXO13
100 100
4
3 8903SXO2 8903SXO14
400
2 8903SYO1 8903SYO16
65 100
4
3 8903SYO2 8903SYO17
600
2 8903SZO1 8903SZO18
65 100
4
3 8903SZO2 8903SZO19
800
2 8903SJO1
30 30
3 8903SJO2