Type S Contactors
Type S Contactor
8502SAO11
Table 32 – Type S Contactors
Catalog Number
Standard Motor Ratings
@ 50/60 Hz (HP)
Max.
Resistive
AC1 Current
(A)
NEMA
Size
Max. Component
SCCR (kA)
1
Three-Phase Circuit
Breakers
@ 480 V
2
Fuses
@ 600 V
200 V 230 V 460 V 575 V
8502SAO12 1.5 1.5 2 2 9 00 100 100
3
8502SBO2 3 3 5 5 18 0 100 100
3
8502SCO2 7.5 7.5 10 10 27 1 100 100
3
8502SDO2 10 15 25 25 45 2 100 100
3
8502SEO2 25 30 50 50 90 3 100 100
3
8502SFO2 40 50 100 100 135 4 100 100
4
8502SGO2 75 100 200 200 270 5 100 100
4
8502SHO2 150 200 400 400 540 6 65 100
4
8502SJO2 — 300 600 600 810 7 30 30
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in
Table 33.
3
When protected by any Class RK5, RK1, T or J fuse, meeting the size limits in Table 33.
4
When protected by any Class T or J fuse, meeting the size limits in Table 33.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
Table 33 – Type S Contactor Maximum Component SCCR
1
Catalog Number
Circuit Breakers @ 480 V
2
Fuses @ 600 V
Max. Breaker Size
(A)
Max. SCCR
(kA)
Max. Fuse Size
(A)
Max. SCCR
(kA)
8502SAO12 70 100 60
3
100
8502SBO2 70 100 60
3
100
8502SCO2 70 100 60
3
100
8502SDO2 100 100 100
3
100
8502SEO2 150 100 200
3
100
8502SFO2 225 100 200
4
100
8502SGO2 400 100 400
4
100
8502SHO2 800 65 600
4
100
8502SJO2 2000 30 1500 30
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
3
When protected by any Class RK5, RK1, T or J fuse.
4
When protected by any Class T or J fuse.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.