Specification

Combination Starter Components Motor Control Solutions
27© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
TeSys™ N Contactors
TeSys N Contactor
T02CN13
Table 30 – TeSys N Contactors
Catalog
Number
Standard Motor Ratings @
50/60 Hz (HP)
Max.
Resistive
AC1
Current (A)
NEMA
Size
Max. Component SCCR (kA)
1
Three-Phase Circuit
Breakers @
480 V
2
Circuit
Breakers @
600 V
2
Fuses @
600 V
3
200 V 230 V 460 V 575 V
T02AN13 1.5 1.5 2 2 9 00 85 50 100
T02BN13 3 3 5 5 18 0 85 50 100
T02CN13 7.5 7.5 10 10 27 1 85 50 100
T02DN13 10 15 25 25 45 2 100 50 100
T02EN13 25 30 50 50 90 3 65 100
T02FN13 40 50 100 100 135 4 65 100
T02GN13 75 100 200 200 270 5 100
T02HN13 150 200 400 400 540 6
T02JN13 300 600 600 810 7
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in
Table 31.
3
When protected by any Class J or CC time-delay fuse meeting the size limits in Table 31.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
Table 31 – TeSys N Contactors Maximum Component SCCR
1
Catalog
Number
Circuit Breakers
@ 480 V
2
Circuit Breakers
@ 600 V
2
Fuses
@ 600 V
3
Max. Breaker
Size (A)
Max. SCCR
(kA)
Max. Breaker
Size (A)
Max. SCCR
(kA)
Max. Fuse
Size (A)
Max.
SCCR (kA)
T02AN13 60 85 60 50 60 100
T02BN13 60 85 60 50 60 100
T02CN13 60 85 60 50 80 100
T02DN13 110 100 110 50 125 100
T02EN13 200 65 200 100
T02FN13 250 65 200 100
T02GN13 600 100
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
3
When protected by any Class J or CC time-delay fuse.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.