Product Brochure
Definite Purpose Control
Contactors, Class 8910 Types DP and DPA
5
04/2014
™
© 1998–2014 Schneider Electric
All Rights Reserved
Factory Modifications
Table 9: Replacement Coils for
Class 8910 Type DPA
Figure 2: Coil Replacement, 50–60 A
(no tools required)
For
Types
Full Load
Amperes
Poles
Class 9998
Type
[1]
Volt-Amperes
Inrush Sealed
DP
50–60 2, 3 DA2 109 10
75–90 2, 3 DA3 214 19
DP11–
DP32
Coils are not replaceable. 33 8
DPA12–
DPA44
Coils are not replaceable. 60 6
[1]
Add the voltage code suffix from Table 10.
For example, a 120 V, 60 Hz coil for an 8910DPA53V02
contactor is 9998DA2V02.
Table 10: Type DPA Coil Voltage Codes
Voltage, 60 Hz Voltage, 50 Hz Voltage Code
24 24 V14
120 110 V02
208–240 220 V09
277 — V04
480 440 V06
600 550 V07 (Type DPA contactors only)
Table 11: Power Terminals
Full Load Amperes
Power Terminals
Type of Lug
Wire Range, AWG
solid or stranded copper wire only
20–30 binder head 16 – 8
40 box lug 14 – 4
50–60 box lug 14 – 2
75–90 box lug 14 – 1/0
Table 12: Mounting Attachment
Description Class 9999 Type
DIN mounting bracket attachment DMB1
Table 13: Factory Modifications
Modification Form (add to the catalog number after the voltage code)
Factory installed auxiliary contacts Contact your local Schneider Electric office.
Pressure wire connectors (20–30 A) Y122
Box lugs (20–30 A) Y239
DIN mounting bracket attached, 35 mm style
(available for 20–60 A devices only)
Y135