TeSys™ GV2P + TeSys D Contactors
TeSys™ GV3P + TeSys D Contactors
Table 71 – TeSys GV2P and TeSys D Contactors for Group Motor
Installations (UL File E164864)
In association with LC1D contactors, suitable for Group Installation
when protected by fuses or a circuit breaker (including multi starter
with GV1G09 or GV2G05 blocks plus GV2G busbars)
Manual
Motor
Starter
Overload
Trip
Range
(A)
Maximum Horsepower Ratings SCCR (kA)
1
1
Ratings apply to circuit with voltages no greater than those listed.
Single-
Phase
Three-Phase
Type of
Contactor
Required
480 V
600Y /
347 V
480 V
with
GV1L3
Limiter
120 V 240 V 208 V 240 V 480 V 600 V
GV2P01 0.10-0.16 - - - - - - LC1D09 or D12 65 42 65
GV2P02 0.16-0.25 - - - - - - LC1D09 or D12 65 42 65
GV2P03 0.25-0.40 - - - - - - LC1D09 or D12 65 42 65
GV2P04 0.40-0.63 - - - - - - LC1D09 or D12 65 42 65
GV2P05 0.63-1 - - - - - 0.5 LC1D09 or D12 65 42 65
GV2P06 1-1.6 - 1/10 - - 0.75 0.75 LC1D09 or D12 65 42 65
GV2P07 1.6-2.5 - 1/6 0.5 0.5 1 1.5 LC1D09 or D12 65 42 65
GV2P08 2.5-4 1/8 1/3 0.75 0.75 2 3 LC1D09 or D12 65 42 65
GV2P10 4-6.3 0.25 0.5 1 1.5 3 5 LC1D09 or D12 65 42 65
GV2P14 6-10 0.5 1.5 2 3 5 7.5 LC1D09 or D12 65 42 65
GV2P16 9-14 0.75 2 3 3 10 10 LC1D12 or D18 22 10 65
GV2P20 13-18 1 3 5 5 10 15 LC1D12 or D18 22 10 65
GV2P21 17-23 1.5 3 5 7.5 15 20 LC1D25 or D32 10 10 65
GV2P22 20-25 2 - 7.5 7.5 15 20 LC1D25 or D32 10 10 65
GV2P32 24-32 2 5 7.5 10 20 25 LC1D25 or D32 5 5 65
GV2P10 with LC1D09
Table 72 – TeSys GV3P and TeSys D Contactors for Group Motor Installations
In association with LC1D contactors, suitable for Group Installation
when protected by fuses or a circuit breaker (including multi starter
with GV3G busbars)
Manual
Motor
Starter
Overload
Trip
Range (A)
Maximum Horsepower Ratings
Type of
Contactor
Required
SCCR (kA)
Single-Phase Three-Phase
480Y /
277 V
600Y /
347 V
120 V 240 V 208 V 240 V 480 V 600 V
GV3P13 9–13 0.5 1.5 3 3 7.5 10
LC1D18, D25, D32,
D40A, D50A, or D65A
65 25
GV3P18 12–18 0.75 2 5 5 10 15
LC1D18, D25, D32,
D40A, D50A, or D65A
65 25
GV3P25 17–25 1.5 3 5 7.5 15 20
LC1D25, D32, D40A,
D50A, or D65A
65 25
GV3P32 23–32 2 5 7.5 10 20 25
LC1D32, D40A,
D50A, or D65A
65 25
GV3P40 30–40 3 10 25 30
LC1D40A, 50A or
65A
65 25
GV3P50 37–50 7.5 10 15 30 40 LC1D50A or 65A 65 25
GV3P65 48–65 5 10 15 20 40 50 LC1D65A or 80 65 25
NOTE: These values are derived from the UL 508 Type F certification (E164871).
GV3P40 with LC1D40A