Installation Guide

Combination Starter Solutions Motor Control Solutions
45© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
UL 508 Type F
Construction Type F is similar to Type E, but uses two devices. The disconnecting
means, motor branch circuit protection, and motor overload relay functions are all
combined into one device, a UL 508 manual self-protected combination controller
while the motor controller is kept separate in the form of a UL 508 contactor.
Schneider Electric offers the following solution for this construction type:
TeSys™ GV2P + TeSys D Contactors
Manual Self-Protected Combination Starter Meeting UL 508 Type F
UL File E164871
Table 67 – Self-Protected Combination Motor Controller using a UL 508 Manual
Self-Protected Combination Controller and a UL 508 Contactor
UL 508 Manual Self-Protected Combination Controller UL 508 Contactor
-TeSys GV2P
-TeSys GV3P
-TeSys D
Table 68 – TeSys GV2P Type F Combination Motor Starter (UL File E164871)
In combination with line spacer GV2GH7 or GV1G09 for stand-alone
starters or line spacer GV1G09 with GV2G busbars for multiple starters
Manual
Self-
Protected
Starter
Overload
Trip
Range (A)
Maximum Horsepower Ratings
Type of
Contactor
Required
SCCR (kA)
Single-Phase Three-Phase
480Y /
277 V
600Y /
347 V
120 V 240 V 208 V 240 V 480 V 600 V
GV2P01 0.10–0.16
LC1D09 or D12 100
LC1D09 100 50
GV2P02 0.16–0.25
LC1D09 or D12 100
LC1D09 100 50
GV2P03 0.25–0.40
LC1D09 or D12 100
LC1D09 100 50
GV2P04 0.40–0.63
LC1D09 or D12 100
LC1D09 100 50
GV2P05 0.63– 1 0.5
LC1D09 or D12 100
LC1D09 100 50
GV2P06 1–1.6 1/10 0.75 0.75
LC1D09 or D12 100
LC1D09 100 50
GV2P07 1.6–2.5 1/6 0.5 0.5 1 1.5
LC1D09 or D12 100
LC1D09 100 50
GV2P08 2.5– 4 1/8 1/3 0.75 0.75 2 3
LC1D09 or D12 100
LC1D09 100 50
GV2P10 4–6.3 0.25 0.5 1 1.5 3 5
LC1D09 or D12 100
LC1D09 100 50
GV2P14 6–10 0.5 1.5 2 3 5 7.5
LC1D09 or D12 100
LC1D09 100 50
GV2P16 9–14 0.75 2 3 3 10 10
LC1D12 or D18 42
LC1D18 50 50
GV2P20 13–18 1 3 5 5 10 15
LC1D12 or D18 42
LC1D18 50 50
GV2P21 17–23 1.5 3 5 7.5 15 20
LC1D25 or D32 42
LC1D25 50 50
GV2P22 20–25 2 7.5 7.5 15 20
LC1D25 or D32 42
LC1D25 50 50
NOTE: Type F ratings only valid at 600Y/347V and 480Y/277V voltages and lower.
TeSys GV2P with TeSys D
GV2GH7 + GV2P10 +
GV2AF3+ LC1D09