UL 508 Overload Relays
TeSys™ K Bimetal Overload Relays
TeSys K Overload Relay
LR2K0304
Table 44 – TeSys LR2K Bimetal Overload Relays
Current
Setting
Range (A)
Class 10 with
Single Phase
Sensitivity
Max. Component SCCR (kA)
1
Circuit Breakers @
480 V
2
Circuit Breakers @
600 V
2
Fuses @ 600 V
3
Max.
Breaker
Size (A)
Max.
SCCR
(kA)
Max.
Breaker
Size (A)
Max.
SCCR (kA)
Max. Fuse
Size (A)
Max.
SCCR
(kA)
0.1–0.16 LR2K0301 15 65 15 25 10 100
0.16–0.23 LR2K0302 15 65 15 25 10 100
0.23–0.36 LR2K0303 15 65 15 25 10 100
0.35–0.54 LR2K0304 15 65 15 25 10 100
0.54–0.8 LR2K0305 15 65 15 25 10 100
0.8–1.2 LR2K0306 15 65 15 25 10 100
1.2–1.8 LR2K0307 15 65 15 25 10 100
1.8–2.6 LR2K0308 15 65 15 25 10 100
2.6–3.7 LR2K0310 15 65 15 25 10 100
3.8–5.5 LR2K0312 15 65 15 25 20 100
5.5–8 LR2K0314 25 65 25 25 30 100
8–11.5 LR2K0316 25 65 25 25 30 100
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
3
When protected by any Class J or CC time-delay fuse.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 65 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.