Installation Guide

Motor Control Solutions Combination Starter Components
30 © 2013–2017 Schneider Electric All Rights Reserved 8536DB0901R09/16
DPA Contactors
Definite Purpose
Type DPA Contactor
8910DPA32
Table 36 – Definite Purpose Type DPA Contactors
1
Catalog
Number
Max.
Inductive
AC3
Current
(A)
Locked Rotor
Amperes
Max.
Resistive
AC1
Current
(A)
Horsepower Ratings
Poles
Max. Component
SCCR (kA)
2
Single-
Phase
Three-Phase
Circuit
Breakers
@ 480 V
3
Fuses
@
600 V
4
230 V
460 V
575 V
115 V
230 V
230 V
460 V
575 V
8910DPA12
20 120 100 80 30 1.5 3 7.5 7.5 7.5
2
100 1008910DPA13 3
8910DPA14 4
8910DPA22
25 150 125 100 35 2 5 10 15 20
2
100 1008910DPA23 3
8910DPA24 4
8910DPA32
30 180 150 120 40 2 5 10 15 20
2
100 1008910DPA33 3
8910DPA34 4
8910DPA42
40 240 200 160 50 3 7.5 10 20 25
2
100 1008910DPA43 3
8910DPA44 4
8910DPA52
50 300 250 200 65 3 10 15 30 30
2
100 100
8910DPA53 3
8910DPA62
60 360 300 240 75 5 10 25 30 30
2
100 100
8910DPA63 3
8910DPA72
75 450 375 300 94 5 15 25 40 40
2
100 100
8910DPA73 3
8910DPA92
90 540 450 360 120 7.5 20 30 50 50
2
100 100
8910DPA93 3
1
Above 240 V, all lines must be switched.
2
Ratings apply to circuits with voltages no greater than those listed.
3
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in
Table 37.
4
When protected by any Class RK5 or J time-delay fuse, meeting the size limits in Table 37.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
Table 37 – Definite Purpose Type DPA Contactor Maximum Component
SCCR
1
Catalog Number
2
Circuit Breaker
@ 480 V
3
Fuse
@ 600 V
4
Max. Breaker
Size (A)
Max. SCCR
(kA)
Max. Fuse
Size (A)
Max. SCCR
(kA)
8910DPA1* 80 100 60 100
8910DPA2* 80 100 60 100
8910DPA3* 80 100 60 100
8910DPA4* 100 100 100 100
8910DPA5* 150 100 200 100
8910DPA6* 150 100 200 100
8910DPA7* 225 100 200 100
8910DPA9* 225 100 200 100
1
Ratings apply to circuits with voltages no greater than those listed.
2
The “*” represents the number of poles. Replace the “*” with a 2 for a 2-pole contactor or a 3 for a 3-pole contactor
or a 4 for a 4-pole contactor.
3
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
4
When protected by any Class RK5 or Class J time-delay fuse.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.