Installation Guide
Combination Starter Components Motor Control Solutions
29© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
Definite Purpose Contactors
DP Compact Contactors
Table 34 – Definite Purpose Type DP Compact Contactors
Catalog
Number
Max.
Inductive
AC3 Current
(A)
Locked Rotor
Amperes
Max. Resistive
AC1 Current
(A)
Max. Component SCCR (kA)
1
Circuit
Breakers
@ 480 V
2
Fuses
@ 600 V
3
277 V 460 V 575 V
1-Pole Contactors
8910DP11 20 120 100 80 30 100 100
8910DP21 25 150 125 100 35 100 100
8910DP31 30 150 125 100 40 100 100
8910DP41 40 240 200 160 50
5
100 100
2-Pole Contactors
4
8910DP12 20 120 100 80 30 100 100
8910DP22 25 150 125 100 35 100 100
8910DP32 30 150 125 100 40 100 100
8910DP42 40 240 200 160 50 100 100
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in Table 35.
3
When protected by any Class J time-delay fuse, meeting the size limits in Table 35.
4
Above 240 V, all lines must be switched.
5
50 A Resistive, maximum 277 V. All others rated 40 A Resistive (above 277 V).
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
Table 35 – Definite Purpose Type DP Compact Contactor Maximum
Component SCCR
1
Catalog
Number
2
Circuit Breaker
@ 480 V
3
Fuse
@ 600 V
4
Max. Breaker
Size (A)
Max. SCCR
(kA)
Max. Fuse
Size (A)
Max. SCCR
(kA)
8910DP1* 80 100 60 100
8910DP2* 80 100 60 100
8910DP3* 80 100 60 100
8910DP4* 100 100 100 100
1
Ratings apply to circuits with voltages no greater than those listed.
2
The “*” represents the number of poles. Replace the “*” with a 2 for a 2-pole contactor or a 3 for a
3-pole contactor.
3
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
4
When protected by any Class J time-delay fuse.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
Definite Purpose
Type DP Compact
Contactor
8910DP22V09