Installation Guide

Combination Starter Components Motor Control Solutions
25© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
TeSys™ F Contactors
TeSys F Contactor
LC1F400
Table 25 – TeSys F Contactors
Catalog
Number
Standard Motor Ratings @
50/60 Hz (hp)
Max.
Inductive
AC3
Current
(A)
Max.
Resistive
AC1
Current
(A)
Continuous
Current
Rating
Max. Component
SCCR (kA)
1
1
Ratings apply to circuits with voltages no greater than those listed.
Three-Phase Circuit
Breakers
@ 480 V
2
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in
Table 26.
Fuses @
600 V
3
3
When protected by any Class J time-delay fuse meeting the size limits in Table 26.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 65 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
208 V 240 V 480 V 600 V
LC1F115 30 40 75 100 115 200 175 65 100
LC1F150 40 50 100 125 150 250 200 65 100
LC1F185 50 60 125 150 185 275 200 65 100
LC1F225 60 75 150 150 225 315 250
LC1F265 60 75 150 200 265 350 285 100
LC1F330 75 100 200 250 330 400 370 100
LC1F400 100 125 250 300 400 500 420
LC1F500 150 200 400 500 500 700 700
LC1F630 250 300 600 800 630 1000 1000
LC1F800 350 400 800 900 800 1000 1000
LC1F780 450 900 900 780 1600 1350
LC1F1000 350 400 900 1000 1250
LC1F1400 1400 1400
LC1F1700 1700 1700
LC1F2100 2100 2100
Table 26 – TeSys F Contactors Maximum Component SCCR
1
Catalog
Number
Circuit Breakers
@ 480 V
2
Fuses
@ 600 V
3
Max. Breaker Size
(A)
Max. SCCR (kA) Max. Fuse Size (A)
Max.
SCCR (kA)
LC1F115 200 65 200 100
LC1F150 250 65 200 100
LC1F185 250 65 400 100
LC1F265 600 100
LC1F330 600 100
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
3
When protected by any Class J time-delay fuse.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.