Installation Guide
Combination Starter Components Motor Control Solutions
23© 2013–2017 Schneider Electric All Rights Reserved8536DB0901R09/16
TeSys D Contactor
LC1D12
Table 21 – TeSys D Contactor Maximum Component SCCR
1
Catalog
Number
Circuit Breakers
@ 480 V
2
Circuit Breakers
@ 600 V
2
Fuses @ 600 V
3
Max. Breaker
Size (A)
Max. SCCR
(kA)
Max.
Breaker
Size (A)
Max. SCCR
(kA)
Max. Fuse
Size (A)
Max. SCCR
(kA)
LC1D09
35 85 35 50 25 100
LC1DT20
LC1D12
36 85 36 50 30 100
LC1DT25
LC1D18
60 85 60 50 40 100
LC1DT32
LC1D25
60 85 60 50 60 100
LC1DT40
LC1D32 60 85 60 50 80 100
LC1D38 60 85 60 50 80 100
LC1D40A
110 100 110 50 90 100
LC1DT60A
LC1D50A 110 100 110 50 110 100
LC1D65A
110 100 110 50 125 100
LC1DT80A
LC1D80 150 100 175 50 175 100
LC1D115 250 100 250 50 250 100
LC1D150 250 100 250 50 300 100
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
3
When protected by any Class J or CC time-delay fuse.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as
the circuit breaker becomes the weakest link.