Installation Guide
Motor Control Solutions Combination Starter Components
22 © 2013–2017 Schneider Electric All Rights Reserved 8536DB0901R09/16
TeSys™ D Contactors
Table 19 – TeSys D 3-Pole Contactors
Catalog
Number
Standard Motor Ratings @ 50/60 Hz (HP)
Max.
Inductive
AC3
Current
(A)
Max.
Resistive
AC1
Current
(A)
No. of
Poles
Continuous
Current
Rating
Max. Component SCCR
(kA)
1
Single-Phase Three-Phase Circuit
Breakers
@ 480 V
2
Circuit
Breakers
@ 600 V
2
Fuses
@
600 V
3
120 V 240 V 208 V 240 V 480 V 600 V N.O. N.C.
LC1D09 1/3 1 2 2 5 7.5 9 20 3 0 25 85 50 100
LC1D12 1/2 2 3 3 7.5 10 12 25 3 0 25 85 50 100
LC1D18 1 3 5 5 10 15 18 32 3 0 32 85 50 100
LC1D25 2 3 7.5 7.5 15 20 25 40 3 0 40 85 50 100
LC1D32 2 5 10 10 20 25 32 50 3 0 50 85 50 100
LC1D38 2 5 10 10 20 25 38 50 3 0 50 85 50 100
LC1D40A 3 5 10 10 30 30 40 60 3 0 60 100 50 100
LC1D50A 3 7.5 15 15 40 40 50 80 3 0 70 100 50 100
LC1D65A 5 10 20 20 40 50 65 80 3 0 80 100 50 100
LC1D80 7.5 15 25 30 60 60 80 125 3 0 110 100 50 100
LC1D95 7.5 15 25 30 60 60 95 125 3 0 110 – – –
LC1D115 — — 30 40 75 100 115 200 3 0 160 100 50 100
LC1D150 — — 40 50 100 125 150 200 3 0 160 100 50 100
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in Table 21 on page 23.
3
When protected by any Class J or CC time-delay fuse meeting the size limits in Table 21 on page 23.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum component SCCR is 100 kA and a 25 kA
rated circuit breaker is used, then the system will be 25 kA as the circuit breaker becomes the weakest link.
Table 20 – TeSys D 4-Pole Contactors
Catalog
Number
Max.
Resistive AC1
Current (A)
No. of Poles Continuous
Current
Rating
Max. Component SCCR (kA)
1
Circuit Breakers @ 480 V
2
Circuit Breakers @ 600 V
2
Fuses @ 600 V
3
N.O. N.C.
LC1DT20 20 4 0 25 85 50 100
LC1D098 20 2 2 25 85 50 100
LC1DT25 25 4 0 25 85 50 100
LC1D128 25 2 2 25 85 50 100
LC1DT32 32 4 0 32 85 50 100
LC1D188 32 2 2 32 85 50 100
LC1DT40 40 4 0 40 85 50 100
LC1D258 40 2 2 40 85 50 100
LC1DT60A 60 4 0 60 100 50 100
LC1DT80A 80 4 0 80 100 50 100
LC1D80004 125 4 0 110 100 50 100
LC1D80008 125 2 2 110 100 50 100
LC1D115004 200 4 0 160 100 50 100
1
Ratings apply to circuits with voltages no greater than those listed.
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only, meeting the size limits in Table 21 on page 23.
3
When protected by any Class J or CC time-delay fuse meeting the size limits in Table 21 on page 23.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum component SCCR is 100 kA and a 25 kA
rated circuit breaker is used, then the system will be 25 kA as the circuit breaker becomes the weakest link.