Installation Guide
Motor Control Solutions Combination Starter Components
20 © 2013–2017 Schneider Electric All Rights Reserved 8536DB0901R09/16
UL 489 Miniature Circuit Breakers and UL 1077 Supplementary Protectors
Multi 9™ Circuit Breakers and Supplementary Protectors
Multi 9 UL 489 Circuit Breaker
M9F42110
Multi 9 UL 1077 Supplementary
Protector M9F22110
Table 13 – Multi 9™ Catalog Numbering System
Range Function Number Poles Amperage
M9 F 42 1 10
Range Function Number Poles Amperage
M9 Multi 9 F MCB
Internal code number
depending on the
standard and electrical
characteristics.
1 1-Pole From 0.5– 63 A
P DPN 2 2-Pole
R RCCB 3 3-Pole
D RCBO 4 4-Pole
V Vigi C60 Add-on
Y Vigi N40 Add-on
C CTRL
Table 14 – Multi 9 UL 489 Breaking Capacity
Number of
Poles
Current Rating (A)
Voltage, AC Voltage, DC
120 V 240 V 277 V 480/277 V 60 V 125 V
1 Pole
1–35 14 14 10 – 10 –
40–63 10 10 – – 10 –
2 Pole
1-35 14 14 10 10 10 10
40-63 10 10 – – – –
3 Pole
1-35 14 14 10 10 – –
40-63 10 10 – – – –
Table 15 – Multi 9 UL 1077 Breaking Capacity
Number of
Poles
Current Rating (A)
Voltage, AC Voltage, DC
120 V 240 V 277 V 480/277 V 60 V 125 V
1 Pole
0.5–35 14 14 10 – 10 –
40–63 10 10 5 – 10 –
2 Pole
1-35 14 14 10 10 10 10
40-63 10 10 5 5 – –
3 and 4 Pole
1-35 14 14 10 10 – –
40-63 10 10 5 5 – –