Installation Guide
Motor Control Solutions Combination Starter Components
40 © 2013–2017 Schneider Electric All Rights Reserved 8536DB0901R09/16
Table 53 – Type S Starters with Motor Logic or TeSys T Overload Relays Max. Component SCCR
1
1
Ratings apply to circuits with voltages no greater than those listed.
Catalog Number
Circuit Breakers @ 480 V
2
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only.
Fuses @ 600 V
Max. Breaker Size (A) Max. SCCR (kA) Max. Fuse Size (A) Max. SCCR (kA)
8536SAO12 70 100 60
3
3
When protected by any Class RK5, RK1, T or J fuse.
100
8536SBO2 70 100 60
3
100
8536SCO2 70 100 60
3
100
8536SDO1 100 100 100
3
100
8536SEO1 150 100 200
3
100
8536SFO1 225 100 200
4
4
When protected by any Class T or J fuse.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the maximum component SCCR is 100 kA and a 25 kA
rated circuit breaker is used, then the system will be 25 kA as the circuit breaker becomes the weakest link.
100
8536SGO1 400 100 400
4
100
8536SHO2 800 65 600
4
100
8536SJO2 2000 30 30 30
Type S Adapted Bimetal Starter
8536SAO12E4050
Table 54 – Type S Starters with Adapted Bimetal Overload Relays
Catalog
Number
Standard Motor Ratings @
50/60 Hz (HP)
Continuous
Current
Rating (A)
NEMA
Size
Max. Component
SCCR (kA)
1
1
Ratings apply to circuits with voltages no greater than those listed.
Three-Phase
Circuit Breakers
@ 480 V
2
2
When protected by any circuit breaker, including thermal-magnetic and magnetic-only. Please refer to TeSys D
overload relays (Table 45 on page 35) for ampacity restrictions.
Fuses
@ 600 V
3
3
When protected by any Class J or CC time-delay fuse. Please refer to TeSys D overload relays (Table 45 on
page 35) for ampacity restrictions.
NOTE: This table lists the maximum SCCR of the component when protected by any circuit breaker or fuse. If the
maximum component SCCR is 100 kA and a 25 kA rated circuit breaker is used, then the system will be 25 kA as the
circuit breaker becomes the weakest link.
208 V 240 V 480 V 600 V
8536SAO12 1.5 1.5 2 2 9 00 65 65
8536SBO2 3 3 5 5 18 0 65 65
8536SCO2 7.5 7.5 10 10 27 1 65 65