Vertically Arranged, Open Type, Two Speed Starters
Vertically arranged starters are used where width limitations prevent the use of the conventional
horizontally arranged device. Such starters may be used to advantage in threaded NEMA Type 7
explosion-proof enclosures, and in multi-motor panels in which other equipment within the enclosure
used limits the available width.
These starters have all the features of the standard horizontally arranged devices, but the two
contactors are in a vertical arrangement. These starters are offered in open type construction only.
Thermal Units
Thermal units should be ordered separately. For selection of thermal units, refer to the Catalog Thermal
Unit Selection Index, Digest or Bulletin SM-416, entitled “Application and Selection of Overload Relays.
Do not use horsepower rating(s) for thermal unit selection. All three phase two speed magnetic starters
require six (6) thermal units, three per speed. Use nameplate FLC’s (Full Load Currents) from motor
nameplate.
Class 8810 — Non-Reversing — Horizontally Arranged Starters
qjGlass Polyester Watertight, Dusttight and Corrosion Resistant Enclosure
50-60 Hertz – 600 Volts Maximum
Type of
Motor
NEMA
Size
Maximum Horsepower Ratings
For Consequent
Pole Motors
For Separate
Winding Motors
200 V 230 V 380 V 460-575 V Type Type
Constant
Horsepower
02233SBW-51SBW-53
1557
1
2
7
1
2
SCW-51 SCW-53
27
1
2
10 20 20 SDW-51 SDW-53
3 20 25 40 40 SEW-51 SEW-53
430406075. . . SFW-53
Constant
Torque or
Variable
Torque
03355SBW-52SBW-54
17
1
2
7
1
2
10 10 SCW-52 SCW-54
210152525SDW-52SDW-54
3 25 30 50 50 SEW-52 SEW-54
4 40 50 75 100 . . . SFW-54
q NEMA Type 4X hubs are included with each starter at no additional cost.
j Combination features available – consult factory.
Class 8810 — Non-Reversing — Vertically Arranged Starters – 50 or 60 Hertz – 600 Volts Maximum
Type of
Motor
NEMA
Size
Maximum Horsepower Ratings
For Consequent
Pole Motors
For Separate
Winding Motors
200 V 230 V 380 V 460-575 V Type Type
Constant
Horsepower
02233SBO-11 SBO-13
1557
1
2
7
1
2
SCO-11 SCO-13
27
1
2
10 20 20 SDO-11 SDO-13
3 20 25 40 40 SEO-11 SEO-13
4 30 40 60 75 SFO-11 SFO-13
Constant
Torque or
Variable
Torque
03355SBO-12 SBO-14
17
1
2
7
1
2
10 10 SCO-12 SCO-14
2 10 15 25 25 SDO-12 SDO-14
3 25 30 50 50 SEO-12 SEO-14
4 40 50 75 100 SFO-12 SFO-14
How to Order:
To Order Specify: Catalog Number
• Class Number
• Type Number
• Coil Voltage Code
• Form(s)
Class Type Coil
Voltage
Code
Form(s)
8810 SCO8 VO6 P1S
AC Two Speed Magnetic Starters
Line Voltage — with Melting Alloy Overload Relays or Solid State Overload Relays – Class 8810