Brochure
Table Of Contents
- AC Magnetic Contactors Class 8502
- AC Magnetic Starters Class 8536
- Class 8502 and 8536 Application Data
- Power Contact Ratings
- Short Circuit Protection
- Capacitor Switching
- Maintenance of Equipment
- Auxiliary Units
- Factory Installed Auxiliary Contacts
- Form Number of Additional Auxiliary Contacts
- Control Circuit Transformers
- Power Poles
- Size 6 Type SH and Size 7 Type SJ Contactors and Starters
- Operation Rates
- Auxiliary Contacts
- Class 8502 Open Type Class 8536 Open Type
- NEMA Type 1 — General Purpose Enclosure
- NEMA Type 1 — General Purpose Enclosure with Form F4T
- NEMA Type 7 & 9 Enclosures for Hazardous Locations Sizes 0-2, Bolted Cover, Cast Iron, Sizes 0-5,...
- NEMA 7 & 9 Bolted Cover, Cast Aluminum
- General Information
- Altitude
- Termination Means
- Auxiliary Contacts
- Auxiliary Contact Units
- section 2 – reversing magnetic starters and contactors
- AC Magnetic Reversing Contactors Class 8702
- AC magnetic reversing starters class 8736
- General Information
- Overload Relays
- MOTOR LOGIC™ Solid State Overload Relay (SSOLR)
- Enclosures
- Holding Circuit Contact
- Coil Voltages
- Mechanical Interlocks
- Auxiliary Contacts
- Type S Accessories
- Power Contact Ratings
- Maintenance of Equipment
- Control Transformer Selection
- Auxiliary Units
- Factory Installed Auxiliary Contacts
- Open Type — 2 or 3-Pole Only
- Auxiliary Contact Units
- General Information
- section 3 – motor starters multi-speed
- Additional Features
- Special Relays for Non-Reversing and Reversing Multispeed Starters
- Thermal Units
- Typical Elementray Diagrams
- Thermal Units
- Vertically Arranged, Open Type, Two Speed Starters
- Thermal Units
- Special Arrangements with Three Devices
- Ordering Information Required
- Thermal Units
- Thermal Units
- Application Data for Types SB-SH
- Control Transformer Selection
- Mechanical Interlock
- Section 1 – magnetic contactors and starters
© 1998 Square D All Rights Reserved
10
5/98
2-Pole Single Phase — 600 Volts AC Maximum — 50-60 Hertz Thermal Units —
One Thermal Unit Required
NEMA
Size
Continuous
Current
Ratings
Motor
Volts
Max.
HP
t
Coil
Voltage
Open
Type
NEMA Type 1
General
Purpose
Enclosure
NEMA Type 4 & 4X
Watertight, Dusttight
Brushed Stainless
Steel Enclosure
NEMA Type 4X
Watertight, Dusttight,
Corrosion-Resistant
Glass-Polyester
Enclosure
Type Type Type Type
00 9
115
1
⁄
3
120 SAO11V02 SAG11V02
Use Size 0 Use Size 0
230 1 240 SAO11V03 SAG11V03
018
115 1 120 SBO1V02 SBG1V02 SBW11V02 SBW21V02
230 2 240 SBO1V03 SBG1V03 SBW11V03 SBW21V03
127
115 2 120 SCO1V02 SCG1V02 SCW11V02 SCW21V02
230 3 240 SCO1V03 SCG1V03 SCW11V03 SCW21V03
1P 36
115 3 120 SCO2V02 SCG2V02 SCW12V02 SCW22V02
230 5 240 SCO2V03 SCG2V03 SCW12V03 SCW22V03
245
115 3 120 SDO6V02 SDG6V02 SDW16V02 SDW26V02
230 7
1
⁄
2
240 SDO6V03 SDG6V03 SDW16V03 SDW26V03
4-Pole, 2-Phase — 600 Volts AC Maximum — 50-60 Hertz — Two Thermal Units Required
NEMA
Size
Continuous
Current
Ratings
Motor
Volts
Max.
HP
t
Coil
Voltage
Open
Type
NEMA Type 1
General
Purpose
Enclosure
NEMA Type 4 & 4X
Watertight, Dusttight
Brushed Stainless
Steel Enclosure
NEMA Type 4X
Watertight, Dusttight,
Corrosion-Resistant
Glass-Polyester
Enclosure
Type Type Type Type
018
Separate Controlj 120 SBO3V02S SBG3V02S SBW13V02S SBW23V02S
200 3 208 SBO3V08 SBG3V08 SBW13V08 SBW23V08
230 3 240 SBO3V03 SBG3V03 SBW13V03 SBW23V03
460 10 480 SBO3V06 SBG3V06 SBW13V06 SBW23V06
575 10 600 SBO3V07 SBG3V07 SBW13V07 SBW23V07
127
Separate Controlj 120 SCO4V02S SCG4V02S SCW14V02S SCW24V02S
200 7
1
⁄
2
208 SCO4V08 SCG4V08 SCW14V08 SCW24V08
230 7
1
⁄
2
240 SCO4V03 SCG4V03 SCW14V03 SCW24V03
460 10 480 SCO4V06 SCG4V06 SCW14V06 SCW24V06
575 10 600 SCO4V07 SCG4V07 SCW14V07 SCW24V07
245
Separate Controlj 120 SDO2V02S SDG2V02S SDW12V02S SDW22V02S
200 10 208 SDO2V08 SDG2V08 SDW12V08 SDW22V08
230 15 240 SDO2V03 SDG2V03 SDW12V03 SDW22V03
460 25 480 SDO2V06 SDG2V06 SDW12V06 SDW22V06
575 25 600 SDO2V07 SDG2V07 SDW12V07 SDW22V07
390
Separate Controlj 120 SEO2V02S SEG2V02S SEW12V02S
Consult Local Square D
Field Office
200 15 208 SEO2V08 SEG2V08 SEW12V08
230 30 240 SEO2V03 SEG2V03 SEW12V03
460 50 480 SEO2V06 SEG2V06 SEW12V06
575 50 600 SEO2V07 SEG2V07 SEW12V07
4 135
Separate Controlj 120 SFO2V02S SFG2V02S SFW12V02S
200 40 208 SFO2V08 SFG2V08 SFW12V08
230 50 240 SFO2V03 SFG2V03 SFW12V03
460 100 480 SFO2V06 SFG2V06 SFW12V06
575 100 600 SFO2V07 SFG2V07 SFW12V07
j 120 Volt Polyphase starters are wired for separate control.
t Coil voltage code must be specified to order this product. Refer to standard coil voltage codes listed in selection table above or additional standard
voltage codes below and insert as shown in the HOW TO ORDER block.
Coil Voltage Codes
Voltage
Code
60 Hz 50 Hz
24q . . . VO1
120 110 VO2
208 . . . VO8
240 220 VO3
480 440 VO6
600 550 VO7
Specify Specify V99
q 24 V coils are not available on Sizes 4-7. On Sizes 00-3, where 24 V
coils are available, Form S (separate control) must be specified.
Full Voltage Starters — NEMA
Selection – Class 8536
Factory Modifications (FORMS) ...............Refer to Catalog 9999CT9701
Application Data ................................................................... Pages 13-16
Dimensions ........................................................................... Pages 17-20
Separate Enclosures (Class 9991) ...........Refer to Catalog 9999CT9701
Replacement Parts (Class 9998) ..............Refer to Catalog 9999CT9701
Type S Accessories (Class 9999) .............Refer to Catalog 9999CT9701
How to Order:
To Order Specify: Catalog Number
• Class Number
• Type Number
• Coil Voltage Code
• Form(s)
Class Type Coil
Voltage
Code
Form(s)
8536 SCG1 VO2 P1
File LR60905
Class 3211-04
File E78351
CCN NLDX
IEC 947-4-1